4.3.13 Setpoint Ramp/Program Set Up Group

Introduction

All models supporting control can be configured to ramp the setpoint between the current local setpoint and a final local setpoint over a timer interval of from 1 minute to 255 minutes.

If the optional Setpoint Program feature is specified at time of purchase, then in addition to this single ramp capability, you can also configure a ramp/soak profile containing up to twelve segments, each with its own time interval.

Setpoint ramp/program group prompts

Table 4-11lists all the function prompts in the setpoint ramp group. The additional prompts associated with the optional twelve-segment Setpoint Program are described in Appendix C.

For a 2-pen recorder, the desired input channel is displayed on the left side of the operator interface. Press

FUNC to select channel.

Press SETUP key until “SPRAMP” appears in the lower display.

Press FUNC key to select the parameters.

Table 4-11 Setpoint Ramp Parameter Definitions

Lower Display

Upper Display

 

 

Parameter

Prompt

Range of Setting

 

 

Definition

 

or Selection

 

 

 

 

 

 

 

 

SP RAMP

 

SINGLE SETPOINT RAMP — Make selection to enable or

 

 

disable the setpoint ramp function. Make sure you

 

 

configure a ramp time and a final setpoint value. “SP

 

 

PROG” must be disabled.

 

ENAB

ENABLE SETPOINT RAMP — Allows the single setpoint

 

 

ramp prompts to be shown.

 

DIS [factory setting]

DISABLE SETPOINT RAMP — Disables the setpoint

 

 

ramp. Allows “SPPROG” option to be selected.

 

 

 

 

 

TI MIN

0 minutes to 255 minutes

SINGLE SETPOINT RAMP TIME — Enter the number of

 

[factory setting = 0]

minutes desired to reach the final setpoint or a single

 

setpoint ramp.

 

 

A ramp time of “0” implies and immediate change of

 

 

setpoint to the final setpoint.

 

 

 

 

 

FINL SP

Within SP limits

SETPOINT RAMP FINAL SETPOINT — Enter the value

 

[factory setting = 0]

desired for the final setpoint. The controller will operate at

 

the setpoint set here when ramp is ended.

 

 

 

SP PROG

ENAB

SETPOINT RAMP/SOAK PROGRAM

 

DIS [factory setting]

Available only with controllers that contain this option.

 

For reasons of convenience, the information for the

 

 

 

 

prompts when SPPROG is enabled are included in

 

 

Appendix C.

 

 

 

 

 

 

 

 

ATTENTION

“SP RAMP” must be disabled for

 

 

 

 

 

 

SPPROG to be available.

 

 

 

 

 