Honeywell DR4300 manual Input Wiring, Power Wiring, Shock Hazard

Models: DR4300

1 262
Download 262 pages 56.21 Kb
Page 39
Image 39

Installation

2.5 Input Wiring

Introduction

This section describes procedures for wiring power, analog inputs, optional digital inputs, and the optional communication link.

2.5.1 Power Wiring

Introduction

Recorder models are available for use with 100 to 240 Vac or 20 Vdc to 27 Vdc power. (See Model Number in Section 1 Overview.)

Procedure

The procedure to connect power wiring is in Table 2-8.

See

Figure 2-9for models without CE Mark.

See

Figure 2-10for models with CE Mark.

WARNING

SHOCK HAZARD

Be sure that the line voltage is OFF before connecting the power wires to the recorder.

Failure to observe this precaution can result in serious personal injury or death.

CAUTION

This equipment is suitable for connection to 100 to 240 Vac (49 to 61 Hz) or 20 to 27 Vac/Vdc power ! supply mains. It is the user’s responsibility to provide a switch and non-time delay (North America), quick-acting, high breaking capacity, Type F, (Europe) 1/2 A, 250 V fuse(s) or circuit-breaker as part of the installation. The switch or circuit-breaker shall be located in close proximity to the recorder,

within easy reach of the operator. The switch or circuit-breaker shall be marked as the disconnecting device for the recorder.

12/03

DR4300 Circular Chart Recorder Product Manual

27

Page 39
Image 39
Honeywell DR4300 manual Input Wiring, Power Wiring, Shock Hazard