DR4300 Circular Chart Recorder Product Manual
 Revision I December
DR4300 Circular Chart Recorder
DR4300 Circular Chart Recorder Product Manual 12/03
 Contacts
Abstract
References
 Symbol Definition
Symbol Definitions
 Contents
 157
141
 161
DR4300 Circular Chart Recorder Product Manual Vii
 225
199
203
211
 Tables
 DR4300 Circular Chart Recorder Product Manual 12/03
 Figures
Page
 Analog inputs
Introduction
Function
CE conformity Europe
 Analog output for control or retransmission
Relay outputs for control and alarms
Timer and totalizer options
Communications
 Construction
Configuration
Self-diagnostics
 Key numbers
Model Number Breakdown
Introduction
Model number format
 Pen Two
Model Number Table I Output
Description Model No Availability
Pen One
 Door Options
Instrument Power/Transmitter Power
Product Configuration
Model Number Table II Instrument Options
 Future
Model Number Table III PEN 1 Options
Model Number Table IV PEN 2 Options
Model Number Table V APPROVALS/CERTIFICATES
 DR4300 Circular Chart Recorder
 All models described
About This Manual
 Trouble?
 What’s in this section?
Pre-installation information
Installation
Overview
 Operating limits
Operating Limits and Condensed Specifications
 Screw terminals 2 piece
Requirements
1000 ft One Pen Purple Two Pen Purple pen 1 and red pen
Calibrated width of 100 mm 4 inches
 Digital Inputs
Transmitter Power
Open Collector Output
Modbus Communication
 Physical considerations
Mounting Considerations and Overall Dimensions
Overall dimensions
Dimensions
 Overview
How to remove knockouts for conduits
Mounting Methods
Introduction
 Step Action
Procedure
Mounting Flush in Panel New Panel Cutout
Mounting Flush in a New Panel Cutout
 Do not tighten the bolt at this time
Panel Mounting Recorder with NEMA4 or Heavy Duty door
Do not tighten the hex bolts at this time
 Side View
Panel Mounting Recorder with NEMA4 or Heavy Duty Door
 Mounting on a 2-inch pipe
Pipe Mounting Procedure
 Mounting Flush on a Surface of Panel or Wall
Mounting on Surface of Panel or Wall
 Recorder grounding
Wiring Prerequisites
Wiring should be performed by qualified personnel
Electrical considerations
 CE conformity special conditions Europe
Taking electrical noise precautions
 Recommended Wiring Routing Models Without CE Mark
Recommended wiring routing
 Recommended Wiring Routing Models With CE Mark
 Wiring Illustrations
Wire bundling recommendations
Wiring Bundling Categories
Wiring diagrams
 Shock Hazard
Input Wiring
Power Wiring
 Procedure for Power Wiring Models
 Power Wiring Models Without CE Mark
 10 Power Wiring Models With CE Mark
 Analog Input Wiring
Analog Input Wiring
 11 Analog Input Wiring
 Digital Inputs Optional
10 Digital Input Wiring
 12 Digital Input Wiring
 Communication Optional
11 Communication Wiring
 13 Communication Wiring
 Discrete Outputs
Output Wiring
 13 Relay Output Wiring 1 or 2 Pen Models
Insulation of output wires
 Electromechanical
 To 30 Vac
 Current Output
14 Current Output Wiring
 16 Current Output Wiring
 15 Transmitter Power Out Wiring
Transmitter Power Out
 TB2
17 Transmitter Power Out Wiring
 Following is a list of topics covered in this section
 Procedure for Configuring Model without Display
Configuration Recording Set Up
Setting Configuration and Input Switches
 Run/Setup Switch
Configuration
Switches
S2 = Reset S3 = Lower S4 = Raise AC Power
 On off off on on off off off Off = Dont care
Configuration Switch S1 Input Switch S6
Summary of Input Set Up Switch S6 Functions
 = off = on
Chart Part R56
 Default setting
 Day Any linear chart
 = off = on
 = off = on
 = off = on
 = off = on
 SW1
 50 to 50 Even 212 24 Hr
 To 100 Even 116 1661-001 Day
 To 200 Even 131 1660-010 24 Hr
 Factory Configuration
 Day 80 to 20 Even 269
 To 100 Even 238 1661-001 Day 239
 IEC Alpha = 0.00391 all RTDs without an asterisk IEC Alpha =
 Off for RTD actuation
Setting SW6 Switch
 Overview
Startup and Operation of Recorder without Display
 Preparing the Recorder for Operation
Preparing the Recorder for Operation
 Graphic
Procedure for Running the Step Test
Running the Optional Step Test
Step Action/Result
 Being careful of the shock hazard at TB1 , place run
Chart step pattern
DR4300 Circular Chart Recorder Step Action/Result Graphic
 Startup
Startup Procedure
Page
 Operation of Recorder with Display and Keypad
 OUT
Displays and indicators
Operator Interface on Recorder with Display and Keypad
INP
 Key functions
 DR4300 Circular Chart Recorder Key Function
Configuration Recording and Output Set Up
 Diagram prompt hierarchy
Configuration Prompts
 For field calibration-see of manual
REMSW1 REMSW2
Blank Toggle
For pen alignment-see of manual
 How to Get Started
 Configuration Tips
Configuration Tips
 Safety precautions
Switch Settings
 SW6 Input Switch
 SW6 switch 2 OFF for RTD
Setting SW6 Burnout Switch Overview
 Location of Switches and Relays
 Step Operation Press Result
Configuration Procedure
Configuration Procedure
 DR4300 Circular Chart Recorder Step Operation Press Result
 Decmal
Input Parameters Set Up Group
Input group prompts
Input Parameter Definitions
 Lin factory setting
100 H*factory setting
 Filter
Example
Bias
 Burnout Protection Input Failure provides most input
None factory setting
 CHT HI
Pen Parameters Set Up Group
Pen group prompts
Pen Parameter Definitions
 Chtspd
Chart Parameters Set Up Group
Chart group prompts
Chart Parameter Definitions
 Total
Totalizer Parameters Set Up Group
Control group prompts
Totalizer Function Definitions
 TOT DP
INP EU Engineering Units of Input Signal
SEC factory setting
TOT EU Engineering Units of Totalized Value
 Cutoff
Rstabl
 Outalg
Control Parameters Set Up Group
ONE factory setting
Control Parameter Definitions
 TIME/CURRENT Duplex Relay = Cool-Similar to
Full factory setting
ON/OFF factory setting
 PROPORTIONAL-DERIVATIVE with Manual
Power UP Controller Mode RECALL-This
PROPORTIONAL-INTEGRAL-DERIVATIVE
 Control Output Direction -In what direction do
Hysteresis Output Relay only is an adjustable
 MAN
Fsmode Failsafe Mode Auto
Failsafe Latching Disabled When the recorder goes
Failsafe Latching Enabled When the recorder goes
 Minutes PER Repeat or Repeats PER Minute
MIN factory setting
Minrpm
 Fuzzy overshoot suppression
Tuning Parameters Set Up Group
Two sets of PID constants
Accutune
 Fuzzy
Tuning group prompts
10 Tuning Parameter Definitions
Fuzzy Overshoot Suppression Feature
 RPM
MIN
 Used for cooling control
Cycle Timer for Relay 1 -Use this to specify
Cycle Timer for Relay 2 -This prompt will be
DR4300 Circular Chart Recorder Product Manual 103
 11 Setpoint Ramp Parameter Definitions
Setpoint Ramp/Program Set Up Group
Setpoint ramp/program group prompts
 Period
Timer Set Up Group
Timer group prompts
12 Timer Parameter Definitions
 13 Alarm Parameter Definitions
Alarms Set Up Group
Alarms group prompts
 A2S1VA
A2S1TY
A2S2TY
 From the alarm setpoint by a value equal to A2 HYS
 Auxout
Auxiliary Output Set Up Group
Auxiliary output group prompts
14 Auxiliary Output Parameter Definitions
 Auxiliary Output High Scaling FACTOR-Use a
Deviation Process Variable minus Setpoint
4mA VA
Auxiliary Output LOW Scaling FACTOR-Use a
 15 Communication Parameter Definitions
Communication Set Up Group
Introductions
Communication group prompts
 Remote switch group prompts
Remote Switch Digital Inputs Set Up Group
 REMSW1
16 Remote Switch Parameter Definitions
Configuration, Startup, and Operation Recorder with Display
DR4300 Circular Chart Recorder Product Manual 113
 17 Display Parameter Definitions
Display Parameter Set Up Group
OFF factory setting
Lockout group prompts
 Lock
Lock Out Parameter Set Up Group
Set this group last
18 Lockout Parameter Definitions
 Keep a record
Configuration Record Sheet
 Recorder TAG Name
DR4300 Circular Chart Recorder Product Manual 117
 19 Limit Control Parameter Definitions
Limit Control Configuration
Special configuration for control and alarms
 Startup of Recorder with Display and Keypad
DR4300 Circular Chart Recorder Product Manual 119
 20 Preparing the Recorder for Operation
Preparing the Recorder for Startup
 Step Press Action/Result
21 Procedure for Running the Step Test
DR4300 Circular Chart Recorder Product Manual 121
Additional automatic self-tests
 Refer to if step test fails
DR4300 Circular Chart Recorder Step Press Action/Result
 Completing Preparation and Startup
Set chart time and apply power Procedure
22 Procedure for Setting Chart Time and Applying Power
DR4300 Circular Chart Recorder Product Manual 123
 Ramtst
Diagnostic tests Tests run automatically
23 Power-Up Diagnostic Tests
Status of tests displayed
 DR4300 Circular Chart Recorder Product Manual 125
Check the displays and keys Procedure
24 Procedure for Testing the Displays and Keys
Key Error message
 Step Operation Press Action/Result
Startup procedure Procedure
25 Procedure for Starting the Recorder
 DR4300 Circular Chart Recorder Product Manual 127
 Operator interface Display
Operation of Recorder with Display and Keypad
Monitoring Your Recorder
 DR4300 Circular Chart Recorder Product Manual 129
Meaning of indicators
26 Meaning of Indicators
Indicator Definition when lit
 27 Lower Display Operating Parameter Labels
Viewing the operating parameters Contents of display
 28 Error Messages
Diagnostic Error Messages
 Overview Actions an operator can initiate
INP Input indicator
Operator Functions
 DR4300 Circular Chart Recorder Product Manual 133
Procedure for selecting manual or automatic mode
29 Procedure for Selecting Automatic or Manual Mode
 30 Procedure for Changing the Control Setpoints
Changing the Control Setpoint Procedure
 DR4300 Circular Chart Recorder Product Manual 135
Viewing and Changing Alarm Setpoints Introduction
31 Procedure for Displaying or Changing the Alarm Setpoints
 FAC or FLD
Selecting Factory or Field Calibration Values Introduction
Present value
 33 Procedure for Resetting Totalizer
Resetting the Totalizer Introduction
Reset procedure
 34 Procedure for Starting Timer
Starting the Timer Introduction
 Limit controller operator interface
Resetting the Limit Controller Introduction
35 Procedure for Resetting Limit Controller
DR4300 Circular Chart Recorder Product Manual 139
 140
 Input and Output Calibration for Recorder with Display
DR4300 Circular Chart Recorder Product Manual 141
 Minimum and maximum range values
Input Calibration Minimum and Maximum Range Values
 RTD
 Equipment Needed for Calibration
Input Calibration Preliminary Information
Equipment needed
 DR4300 Circular Chart Recorder Product Manual 145
Disconnect the field wiring
 General set up procedure
Input Calibration Set Up and Wiring
General Calibration Set Up
DIP switch settings
 DR4300 Circular Chart Recorder Product Manual 147
Thermocouple Inputs Using a Compensated Calibrator
 Thermocouple Inputs Using an Ice Bath or Ice Point Reference
 DR4300 Circular Chart Recorder Product Manual 149
RTD Resistance Temperature Detector Inputs
Set Up Wiring Procedure for Calibrating RTD Inputs
 Millivolts, Volts and Milliamps inputs
 DR4300 Circular Chart Recorder Product Manual 151
Input Calibration Procedure
Calibration procedure sequence
Input Calibration Procedure Sequence
 Repeat this procedure for the other pen, if required
 Calibrator connections
10 Set Up Wiring Procedure for Current Proportional Output
DR4300 Circular Chart Recorder Product Manual 153
Current Output Calibration
 11 Procedure for Calibrating Current Output
 Disp SET
DR4300 Circular Chart Recorder Product Manual 155
 156
 DR4300 Circular Chart Recorder Product Manual 157
Routine Maintenance
 Pens to the chart
Replacing the Chart
Procedure for Replacing the Chart
Chart hub
 Replacing the Ink Cartridge
Procedure for Replacing the Ink Cartridge
DR4300 Circular Chart Recorder Product Manual 159
 Maximizing Pen Life
Maximizing Pen Life
Steps for maximizing pen life
 Topic
DR4300 Circular Chart Recorder Product Manual 161
 Hardware and software related problems
Types of problems
Installation related problems
Application related problems
 Symptom Subsection
Observable Symptoms of Failure
Symptoms
Observable Symptoms of Failure
 Troubleshooting Procedures
 DR4300 Circular Chart Recorder Product Manual 165
Recorder Failure Troubleshooting
Troubleshooting Recorder Failure Symptoms
 Troubleshooting Pen Trace Failure Symptoms
Pen Trace Troubleshooting
 DR4300 Circular Chart Recorder Product Manual 167
Chart Rotation Troubleshooting
Troubleshooting Chart Rotation Failure Symptoms
 Troubleshooting Erratic Pen Movement Symptoms
Troubleshooting Erratic Pen Movement
 Step Action Graphic
Procedure for Pen Alignment
DR4300 Circular Chart Recorder Product Manual 169
Alignment of Pen at Zero and 100 %
 DR4300 Circular Chart Recorder Step Action Graphic
 DR4300 Circular Chart Recorder Product Manual 171
Troubleshooting and Pen Alignment of Recorder with Display
 172
 Troubleshooting Aids
 Tests run automatically
Self Diagnostics
Power up tests
Power-Up Diagnostic Tests
 View Status of Tests
Procedure for Displaying the Results of Self-Diagnostics
DR4300 Circular Chart Recorder Product Manual 175
 All relevant messages are displayed
Error Messages
Background Tests
 DR4300 Circular Chart Recorder Product Manual 177
Error Messages
Troubleshooting and Pen Alignment Recorder with Display
Configuration, Startup, and Operation Recorder with Display
 P2 ERR
P1 ERR
 DR4300 Circular Chart Recorder Product Manual 179
 180
 DR4300 Circular Chart Recorder Product Manual 181
 Recorder with Display for instructions for
 Operation of Recorder with Display Subsection
DR4300 Circular Chart Recorder Product Manual 183
Operation of Recorder with Display
 Operation of Recorder with Display for procedure
Troubleshooting the Keypad and Display
10 Troubleshooting Keypad and/or Display Failure Symptoms
 Refer to Replacing Hardware
Troubleshooting Relay Output
11 Troubleshooting Relay Output Failure Symptoms
DR4300 Circular Chart Recorder Product Manual 185
 12 Troubleshooting External Alarm Function Failure Symptoms
Troubleshooting External Alarm Function
Troubleshooting Remote Switch Digital Input Function
 DR4300 Circular Chart Recorder Product Manual 187
Troubleshooting Modbus Communications
14 Troubleshooting Modbus Communications
 Alignment of Pen at Zero and Span
15 Procedure for Aligning Pen at Zero and Span
 DR4300 Circular Chart Recorder Product Manual 189
Troubleshooting and Pen Alignment Recorder with Display Step
 190
 DR4300 Circular Chart Recorder Product Manual 191
Parts List
 Exploded Views
Door assembly
 DR4300 Circular Chart Recorder Product Manual 193
Chart plate
 Recorder Components
Basic recorder components without options
 Parts Not Shown
Upgrade PROMs
DR4300 Circular Chart Recorder Product Manual 195
Basic Recorder Parts
 Chart
 DR4300 Circular Chart Recorder Product Manual 197
DR4300 Recorder Non-CE Mark Internal Cabling Diagram
 198
 Appendix a Accuracy
DR4300 Circular Chart Recorder Model Product Manual 199
Reference accuracy
 Table A-1 Typical Reference Accuracy
Typical Reference Accuracy
 Factory Temp Stability Actuations
± Degrees With Error Per 1 Degree Field Calibration Linear
DR4300 Circular Chart Recorder Model Product Manual 201
Types of Input Range
 202
 DAY
Single Range Charts
Table B-1 10-inch Single Range Chart Part Numbers
 W5W26 Thermocouple
DR4300 Circular Chart Recorder Chart Type Range Units 24 HR
 12/03 DR4300 Circular Chart Recorder Product Manual 205
 RTD-PT100 a=0.00391
 RTD-PT100 a=0.00385
DR4300 Circular Chart Recorder Product Manual 207
 Calibration Range 24 HR
Dual Range Charts
Table B-2 10-inch Dual Range Chart Part Numbers
 DR4300 Circular Chart Recorder Product Manual 209
Appendix B Available 10-inch Charts Calibration Range 24 HR
 Minimum purchase required
DR4300 Circular Chart Recorder Calibration Range 24 HR
 Appendix C Setpoint Ramp/Soak Programming and Operation
DR4300 Circular Chart Recorder Product Manual 211
 Program Contents
 End segment number for each program
Guaranteed soak
Soak segments
Start segment number for each program
 Ramp/soak profile example
Drawing a Ramp/Soak Profile
 Profile graphs
DR4300 Circular Chart Recorder Product Manual 215
 216
 Profile worksheet
DR4300 Circular Chart Recorder Product Manual 217
 Recycl
Setpoint Program Prompt Hierarchy
Table C-1 Prompt Hierarchy and Available Selections
END
 SG2 SP
Rpunit
END ST
SG1 RP
 SG24SP
Or hour if Rpunit = EU-M Or EU-H Factory setting =
Limits factory setting =
SG23RP
 Table C-2 Run/Monitor Functions
Run/Monitor the Program
Run/Monitor functions
 XX HH . MM
 REC.X
 224
 DR4300 Circular Chart Recorder Product Manual 225
Appendix D Using Accutune
 Table D-1 Procedure for Starting Accutune
Starting and Stopping Tuning with Accutune
 DR4300 Circular Chart Recorder Product Manual 227
Using Accutune with Duplex Heat/Cool Control
Table D-2 Procedure for Using Accutune for Duplex Control
Step Press Action/Result Heating Tuning
 Until the value of Setpoint 2 is at the desired value within
 Foreign Language Safety Instructions
 DR4300 Circular Chart Recorder
 DR4300 Circular Chart Recorder Product Manual 231
 232
 DR4300 Circular Chart Recorder Product Manual 233
 234
 DR4300 Circular Chart Recorder Product Manual 235
 236
 DR4300 Circular Chart Recorder Product Manual 237
 238
 ¹¬¸ª¸ ¸»ª¸
 240
 DR4300 Circular Chart Recorder Product Manual 241
Appendix F Honeywell Service Centers
 242
 Index
DR4300 Circular Chart Recorder Product Manual 243
 Ctralg parameter, 95, 100, 102, 103 current outputs
 Knockout locations, 16
DR4300 Circular Chart Recorder Product Manual 245
 Status set up group, 175 step test
 TB5 terminal
DR4300 Circular Chart Recorder Product Manual 247
 248
Page