DR4300 Circular Chart Recorder

Lower Display

Upper Display

 

 

Parameter

Prompt

Range of Setting

 

 

Definition

 

or Selection

 

 

 

 

 

 

BRNOUT

 

BURNOUT PROTECTION (INPUT FAILURE) provides most input

 

 

types with upscale or downscale protection if the input fails. Note

 

 

that if the input fails, error message “INP FL” will be on the lower

 

 

display.

 

 

 

 

 

 

 

 

ATTENTION

Refer to Subsection 4.5 for information about the

 

 

 

 

 

 

interaction of the value of this parameter and the setting of switch 2

 

 

on SW6.

 

NONE [factory setting]

NO BURNOUT—Failsafe output applied for failed input.

 

UP

UPSCALE BURNOUT will make the indicated PV signal go to

 

 

overrange value when input fails. Control algorithm will use

 

 

overrange value when calculating output.

 

DOWN

DOWNSCALE BURNOUT will make the indicated PV signal go to

 

 

underrange value when input fails. Control algorithm will use

 

 

underrange value when calculating output.

 

 

 

 

 

NOTE: For recorders with the FM Limit Approved Option the INPUT configuration does not provide a burnout selection. However, if a HI limit is configured and the input opens, the input reading will go Upscale and the lower display will alternate between: INP#, Limit, and INP FL.

If a LO limit is configured and the input opens, the input reading will go down scale and the lower display will alternate between: INP#, Limit, and INP FL.

88

DR4300 Circular Chart Recorder Product Manual

12/03

Page 100
Image 100