DR4300 Circular Chart Recorder

Procedure

The procedure for calibrating the current proportional output is listed in Table 5-11.Make sure “LOCK” in the Set Up group is set to “NONE.”

For display recorders with 2 pens, be sure the correct input is on display—INP 1 or INP 2 indicator is lit.

Press

FUNC

key to change input on display to agree with the control loop output to be calibrated.

Table 5-11 Procedure for Calibrating Current Output

Step

Description

Press

Action/Result

1

Enter Calibration Mode

SET

 

Upper Display

 

 

 

CAL

 

 

UP

 

 

 

 

 

 

 

 

 

 

 

 

until you see

Lower Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CURENT

 

 

 

 

 

 

If “CAL” doesn’t appear or prompt access is denied, check

 

 

 

 

 

the “LOCK” configuration.

 

 

 

 

 

 

2

Calibrate 0 %

 

 

You will see:

FUNC

 

 

 

 

 

Upper Display

 

 

 

 

 

 

 

a value (approximately 365)

 

 

 

 

 

 

 

 

 

 

 

 

Lower Display

 

 

 

 

 

ZERO

 

 

 

 

 

 

 

 

 

 

 

 

Until the desired 0 % output is read on the milliammeter.

 

 

 

 

 

 

 

 

 

 

Use the values shown below depending on the action of

 

 

 

 

 

your recorder.

 

 

 

or

 

 

 

 

 

 

 

 

 

 

 

3

Calibrate 100 %

FUNC

Stores the 0 % value and, you will see:

 

 

 

 

Upper Display

 

 

 

 

 

 

a value (approximately 1800)

 

 

 

 

 

 

 

 

 

Lower Display

 

 

 

 

 

SPAN

 

 

 

 

 

 

 

 

 

 

Until the desired 100 % output is read on the milliammeter.

 

 

 

 

 

 

 

 

Use the values shown below depending on the action of

 

 

 

 

your recorder.

 

 

 

or

 

 

 

 

 

 

 

 

 

 

154

DR4300 Circular Chart Recorder Product Manual

12/03

Page 166
Image 166
Honeywell manual Procedure for Calibrating Current Output, DR4300 Circular Chart Recorder