4.3.22 Limit Control Configuration

Special configuration for control and alarms

The DR4300 is available as a limit controller. Most set up groups described in Subsections 4.3.7 through

4.3.20apply to limit control, and are configured for the limit controller the same way they are for other recorders.

The exceptions are:

Control set up group contains special parameters for limit control in place of those described in Subsection 4.3.11. The limit control set up parameters that replace those in Subsection 4.3.11 are listed in Table 4-19.

Alarm 1 is not available.

Table 4-19 Limit Control Parameter Definitions

Lower Display

 

Upper Display

Parameter

Prompt

Range of Setting

Definition

 

 

or Selection

 

 

 

 

 

LIMIT

 

 

TYPE OF LIMIT CONTROL

 

HI

[factory setting]

HI — Limit action occurs when PV exceeds SP.

 

LO

 

LO — Limit action occurs when PV is less than SP.

 

 

 

 

POWRUP

 

 

POWER UP STATE

 

NORM

 

NORM — Normal limit control on power up.

 

RST

[factory setting]

RST — Powers up in limit state. Recorder will not begin

 

 

 

normal limit control until RESET key is pressed.*

 

 

 

SP HI

–999 to 9999

SETPOINT HIGH RANGE LIMIT —This parameter

 

[factory setting = 100]

prevents the local setpoint from going above the value

 

specified here. The setting must be equal to or less than

 

 

 

the upper range of the input.

 

 

 

SP LO

–999 to 9999

SETPOINT LOW RANGE LIMIT—This parameter

 

[factory setting = 0]

prevents the local setpoint from going below the value

 

specified here. The setting must be equal to or greater

 

 

 

than the lower range of the input.

 

 

 

 

XRSET

 

 

EXTERNAL RESET—Use this parameter to enable or

 

 

 

disable resetting the limit controller (taking it out of the

 

 

 

limit state) using Remote Switch 1 (digital

 

 

 

input 1).

 

DIS [factory setting]

DIS — When external reset is disabled, the limit controller

 

 

 

can be reset only by pressing the MAN/AUTO/RESET

 

 

 

key on the recorder.

 

ENAB

 

ENAB — When external reset is enabled, the limit

 

 

 

controller can be reset two ways: by pressing the

 

 

 

MAN/AUTO/RESET key on the recorder, or by turning on

 

 

 

digital input 1 (contact closed).

 

 

 

 