DR4300 Circular Chart Recorder

C.4 Setpoint Program Prompt Hierarchy

Table C-1lists all the function prompts for Setpoint Program data configuration in the order of their appearance. These prompts are available when SPPROG is enabled in the SPRAMP set up group described in Section 4.

All parameters may be changed while the program is disabled or in HOLD.

Table C-1 Prompt Hierarchy and Available Selections

Lower Display

Upper Display

Parameter

Prompt

Range of Setting

Definition

 

or Selection

 

 

 

 

SPPROG

 

SETPOINT PROGRAMMING—This must be set to ENAB

 

 

for the setpoint program feature to work, and for the

 

 

associated operating parameters to be displayed.

 

 

SPRAMP must be disabled. (See Section 4.)

 

DIS

DIS—Disabled

 

ENAB

ENAB—Enabled

 

 

 

START 1

1,3,5,7,9,11,13,15,17,19,

START SEGMENT FOR PROGRAM 1—Enter the

 

21,23 [factory setting=1]

number of the first segment in Program 1.

 

 

 

END 1

2,4,6,8,10,12,14,16,18,20,22,

END SEGMENT FOR PROGRAM 1—Enter the number

 

24 [factory setting=6]

of the last segment in Program 1.

 

 

 

START 2

1,3,5,7,9,11,13,15,17,19,

START SEGMENT FOR PROGRAM 2—Enter the

 

21,23 [factory setting=7]

number of the first segment in Program 2.

 

 

 

END 2

2,4,6,8,10,12,14,16,18,20,22,

END SEGMENT FOR PROGRAM 2—Enter the number

 

24 [factory setting=12]

of the last segment in Program 2.

 

 

 

START 3

1,3,5,7,9,11,13,15,17,19,

START SEGMENT FOR PROGRAM 3—Enter the

 

21,23 [factory setting=13]

number of the first segment in Program 3.

 

 

 

END 3

2,4,6,8,10,12,14,16,18,20,22,

END SEGMENT FOR PROGRAM 3—Enter the number

 

24 [factory setting=18]

of the last segment in Program 3.

 

 

 

START 4

1,3,5,7,9,11,13,15,17,19,

START SEGMENT FOR PROGRAM 4—Enter the

 

21,23 [factory setting=19]

number of the first segment in Program 4.

 

 

 

END 4

2,4,6,8,10,12,14,16,18,20,22,

END SEGMENT FOR PROGRAM 4—Enter the number

 

24 [factory setting=24]

of the last segment in Program 4.

 

 

 

RECYCL

0 to 99

RECYCLES—Enter the number of times the program

 

[factory setting=0]

selected for execution will be repeated.

 

 

 

SOKDEV

–99.9 to 99.9 engineering

SOAK DEVIATION—Enter the acceptable deviation from

 

units

setpoint during a soak cycle. If the PV differs from the

 

[factory setting=0.00]

setpoint by more than the value of SOKDEV, soak time is

 

frozen.

 

 

There are no guaranteed soaks if SOKDEV = 0.

 

 

 

218

DR4300 Circular Chart Recorder Product Manual

12/03

Page 230
Image 230
Honeywell DR4300 manual Setpoint Program Prompt Hierarchy, Table C-1 Prompt Hierarchy and Available Selections, End, Recycl