DR4300 Circular Chart Recorder

C.2 Program Contents

What you will configure

You will configure all the data that is relevant to each ramp and soak segment for a given setpoint versus time program (profile). The recorder will prompt you through the sequence of segments and associated functions. All prompts are listed, in sequence, in Table C-1.

Ramp unit

The ramp unit selection determines the engineering units for the ramp segments.

The selections are:

TIME = Hours:Minutes

EU-H = Degrees/Hour OR EU-M = Degrees/Minute

Recycle number

The recycle number allows the program to recycle a specified number of times from beginning to end.

Range = 0 to 99

Program state

The program state selection determines the program state after completion.

The selections are:

DIS = program is disabled

HOLD = program on hold

Ramp time or rate segments

A ramp segment is used to change the setpoint to the next soak setpoint value in the program.

Ramps are odd-numbered segments. Segment 1 will be the initial ramp.

Ramps are specifed in terms of either:

TIME* - Hours:Minutes

Range = 0-99 hr:59 min

or

 

EU-M* - Degrees/Minute

Range = 0 to 999

EU-H* - Degrees/Hour

 

*The selection of time or rate is made at prompt “RP UNIT”. Set this prompt before entering any Ramp information.

ATTENTION

Entering “0” will imply an immediate step change in setpoint to the next soak.