Configuration, Startup, and Operation of Recorder with Display

Tuning group prompts

Table 4-10lists all the parameters in the tuning set up group.

For a 2-pen recorder, the desired input channel is displayed on the left side of the operator interface. Press FUNC to select channel.

Press SETUP key until “TUNING” appears in the lower display.

Press FUNC key to select the parameters.

ATTENTION

Appendix D contains instructions for using Accutune II for automatic tuning.

Table 4-10 Tuning Parameter Definitions

Lower Display

Upper Display

 

 

Parameter

Prompt

Range of Setting

 

 

Definition

 

or Selection

 

 

 

 

 

 

 

 

FUZZY

DIS [factory setting]

FUZZY OVERSHOOT SUPPRESSION FEATURE

 

DISABLE—Disables fuzzy overshoot suppression

 

ENAB

ENABLE—The recorder will use fuzzy logic to suppress

 

 

or mimimize any overshoot that may occur as a result of

 

 

the existing tuning parameters. It does NOT change the

 

 

parameters.

 

 

 

 

 

TUNE

DIS [factory setting]

ACCUTUNE II—On demand tuning algorithm

 

DISABLE—Disables ACCUTUNE II

 

ENAB

ENABLE—TuneOF will be displayed as a status

 

 

message. Use the Increment or Decrement key to

 

 

toggle status to TuneON. New PID parameters will be

 

 

entered automatically when tuning is complete.

 

 

 

 

 

AT ERR

no message under normal

ACCUTUNE II Error Code—Displays AbRT if “TUNE”

 

circumstances

has been aborted manually.

 

AbRT read only message

See Appendix D.

 

displayed if tuning has been

 

 

 

 

manually aborted

 

 

 

 

 

 

PB

0.1 % to 999.9 %

PROPORTIONAL BAND or GAIN—Which of these

or

or

prompts is displayed depends on the selection made for

GAIN

0.1 to 999.9

control group parameter “PBorGN” (proportional band or

 

[factory setting = 1.0]

gain). Both proportional band and gain are ways of

 

expressing the proportional component of control. See

 

 

the description of control group parameter “PBorGN” for

 

 

details concerning the two terms.

 

 

 

 

 

 

 

 

ATTENTION

If control group parameter “OUTALG”

 

 

is “RLYD” (relay duplex), “Tcur” (time/current duplex), or

 

 

“CurT” (current/time duplex), and you are using the

 

 

recorder in a heat/cool application, PB or GAIN is used

 

 

for heat control. Cooling control would use PB2 or GAIN

 

 

2 described later in this table.

 

 

 

 

 

12/03

DR4300 Circular Chart Recorder Product Manual

101