Configuration, Startup, and Operation

 

 

 

 

 

of Recorder with Display

 

 

 

 

 

 

 

 

Lower Display

 

Upper Display

Parameter

 

 

Prompt

 

Range of Setting

Definition

 

 

 

 

or Selection

 

 

 

A1S1HL

 

 

ALARM 1 SETPOINT 1 STATE—Select whether you

 

 

 

 

 

want the alarm type chosen in prompt "A1S1TY" to alarm

 

 

 

HI

 

high or low.

 

 

 

 

HI ALARM—Relay coil is de-energized when the PV is

 

 

 

LO

[factory setting]

above the setpoint.

 

 

 

LO ALARM—Relay coil is de-energized when the PV is

 

 

 

 

 

below the setpoint.

 

 

 

 

 

 

 

 

A1S2HL

 

 

ALARM 1 SETPOINT 2 STATE—Select whether you

 

 

 

 

 

want the alarm type chosen in prompt "A1S2TY" to alarm

 

 

 

HI

[factory setting]

high or low.

 

 

 

HI ALARM—Relay coil is de-energized when the PV is

 

 

 

LO

 

above the setpoint.

 

 

 

 

LO ALARM—Relay coil is de-energized when the PV is

 

 

 

 

 

below the setpoint.

 

 

 

 

 

 

 

A1 HYS

0.0 % to 100.0 % of input

ALARM 1 HYSTERESIS—This is an adjustable

 

 

 

span

hysteresis provided on alarm 1 that activates at exactly

 

 

 

[factory setting = 0]

the alarm setpoint when the alarm is OFF. When the

 

 

 

alarm is ON, it will not deactivate until the variable is away

 

 

 

 

 

from the alarm setpoint by a value equal to A1 HYS.

 

 

 

 

 

Configure the hysteresis as a percent of input range

 

 

 

 

 

span.

 

 

 

 

 

 

 

A2S1TY

Same as A1S1TY

ALARM 2 SETPOINT 1 TYPE—Select what you want

 

 

 

 

 

Setpoint 1 of Alarm 2 to represent. The selections are the

 

 

 

 

 

same as “A1S1TY”.

 

 

 

 

 

 

 

A2S2TY

Same as A1S1TY

ALARM 2 SETPOINT 2 TYPE—Select what you want

 

 

 

 

 

Setpoint 2 of Alarm 2 to represent. The selections are the

 

 

 

 

 

same as “A1S1TY”.

 

 

 

 

 

 

 

A2S1VA

–999 to 9999

ALARM 2 SETPOINT 1 VALUE—This is the value at

 

 

 

[factory setting = 100]

which you want the alarm type chosen in prompt

 

 

 

"A2S1TY" to actuate. The appropriate value depends on

 

 

 

 

 

what the setpoint has been configured to represent.

 

 

 

 

 

 

 

A2S2VA

–999 to 9999

ALARM 2 SETPOINT 2 VALUE—This is the value at

 

 

 

[factory setting = 100]

which you want the alarm type chosen in prompt

 

 

 

"A2S2TY" to actuate. The appropriate value depends on

 

 

 

 

 

what the setpoint has been configured to represent.

 

 

 

 

 

 

 

 

A2S1HL

 

 

ALARM 2 SETPOINT 1 STATE—Select whether you

 

 

 

 

 

want the alarm type chosen in prompt "A2S1TY" to alarm

 

 

 

HI

 

high or low.

 

 

 

 

HI ALARM—Relay coil is de-energized when the PV is

 

 

 

LO

[factory setting]

above the setpoint.

 

 

 

LO ALARM—Relay coil is de-energized when the PV is

 

 

 

 

 

below the setpoint.

 

 

 

 

 

 

 

 

A2S2HL

 

 

ALARM 2 SET POINT 2 STATE—Select whether you

 

 

 

 

 

want the alarm type chosen in prompt "A2S2TY" to alarm

 

 

 

HI

[factory setting]

high or low.

 

 

 

HI ALARM—Relay coil is de-energized when the PV is

 

 

 

LO

 

above the setpoint.

 

 

 

 

LO ALARM—Relay coil is de-energized when the PV is

 

 

 

 

 

below the setpoint.

 

 

 

 

 

 

 

12/03

DR4300 Circular Chart Recorder Product Manual

107

Page 119
Image 119
Honeywell DR4300 manual A2S1TY, A2S2TY, A2S1VA