Honeywell DR4300 manual Rpunit, End St, SG1 RP, SG2 SP, SG2 TI, SG3 RP, SG4 SP, SG4 TI

Models: DR4300

1 262
Download 262 pages 56.21 Kb
Page 231
Image 231

 

 

 

 

Appendix C - Setpoint Ramp/Soak

 

 

 

 

 

Programming and Operation

 

 

 

 

 

 

 

 

Lower Display

 

Upper Display

Parameter

 

 

Prompt

 

Range of Setting

Definition

 

 

 

 

or Selection

 

 

 

 

 

 

 

 

 

RPUNIT

 

 

RAMP UNITS—The selection you make here will

 

 

 

 

 

determine whether the ramp segments will be configured

 

 

 

 

 

in terms of time or in terms of rate.

 

 

 

TIME

[factory setting]

TIME—Ramps will be configured in hrs:min.

 

 

 

EU-M

 

Engineering Units per Minute—Ramps will be

 

 

 

 

 

configured as a rate in EU-M.

 

 

 

EU-H

 

Engineering Units per Hour—Ramps will be configured

 

 

 

 

 

as a rate in EU-H.

 

 

 

 

 

 

 

 

END ST

DIS

[factory setting]

END STATE—Specify whether the program will be

 

 

 

HOLD

disabled after execution, or be placed in Hold.

 

 

 

 

 

 

 

SG1 RP

0 to 99 hours:0 to 59 min

SEGMENT 1 RAMP VALUE—Enter the ramp time or

 

 

 

(if RPUNIT = TIME)

ramp value for Segment 1.

 

 

 

or

 

Whether ramp segments are configured in terms of

 

 

 

0 to 999 degrees per minute

time or rate depends on whether RPUNIT is set to

 

 

 

TIME or EU-M/EU-H.

 

 

 

or hour (if RPUNIT = EU-M

 

 

 

 

 

 

 

or EU-H)

 

 

 

 

[factory setting=0.00]

 

 

 

 

 

 

 

 

SG2 SP

range depends on setpoint

SEGMENT 2 SETPOINT—Enter the setpoint for Segment

 

 

 

limits [factory setting=0]

2.

 

 

 

 

 

 

 

SG2 TI

0 to 99 hours:0 to 59 min

SEGMENT 2 TIME—Enter the duration for Segment 2

 

 

 

[factory setting=0]

 

 

 

 

 

 

 

 

SG3 RP

0 to 99 hours:0 to 59 min

SEGMENT 3 RAMP VALUE—Enter the ramp time or

 

 

 

(if RPUNIT = TIME)

ramp value for Segment 3.

 

 

 

or

 

 

 

 

 

0 to 999 degrees per minute

 

 

 

 

or hour (if RPUNIT = EU-M

 

 

 

 

or EU-H)

 

 

 

 

[factory setting=0.00]

 

 

 

 

 

 

 

 

SG4 SP

range depends on setpoint

SEGMENT 4 SETPOINT—Enter the setpoint for Segment

 

 

 

limits [factory setting 0]

4.

 

 

 

 

 

 

 

SG4 TI

0 to 99 hours:0 to 59 min

SEGMENT 4 TIME—Enter the duration for Segment 4

 

 

 

[factory setting=0]

 

 

 

 

 

 

 

 

12/03

DR4300 Circular Chart Recorder Product Manual

219

Page 231
Image 231
Honeywell DR4300 manual Rpunit, End St, SG1 RP, SG2 SP, SG2 TI, SG3 RP, SG4 SP, SG4 TI