DR4300 Circular Chart Recorder

Lower Display

Upper Display

 

 

Parameter

Prompt

Range of Setting

 

 

Definition

 

or Selection

 

 

 

 

 

 

 

 

RATE T

0.08 to 10.00 minutes

RATE—Rate action affects the recorder’s output

 

0.08 or less = OFF

whenever the deviation between setpoint and process

 

[factory setting = 0.0]

variable is changing. It affects it more when the deviation

 

is changing faster. (This is the “derivative” component of

 

 

control.)

 

 

 

 

 

 

 

 

 

ATTENTION

If control group parameter “OUTALG”

 

 

 

 

 

 

is “RLYD” (relay duplex), “Tcur” (time/current duplex), or

 

 

“CurT” (current/time duplex), and you are using the

 

 

recorder in a heat/cool application, RATE T is used for

 

 

heat control. Cooling control would use RATE2T

 

 

described later in this table.

 

 

 

I MIN

0.02 to 50.00

RESET IN MINUTES PER REPEAT or RESET IN

or

[factory setting = 0.02]

REPEATS PER MINUTE—Which of these prompts is

I RPM

displayed depends on the selection made for control

 

 

group parameter “MINRPM”.

 

 

Reset adjusts the recorder’s output taking into

 

 

consideration both the size of the deviation (SP-PV) and

 

 

the duration of the deviation. (This is the “integral”

 

 

component of control.) The amount of corrective action

 

 

depends on the value of PB or GAIN.

 

 

The reset value specified here determines how many

 

 

times proportional action is repeated per minute

 

 

(I RPM) or the length (in minutes) of the reset action (I

 

 

MIN). For example, if I MIN = .5, it is the same as if I

 

 

RPM = 2. The result is the same; two resets are

 

 

performed in every minute.

 

 

 

 

 

 

 

 

ATTENTION

If control group parameter “OUTALG”

 

 

is “RLYD” (relay duplex), “Tcur” (time/current duplex), or

 

 

“CurT” (current/time duplex), and you are using the

 

 

recorder in a heat/cool application, I MIN or I RPM is

 

 

used for heat control. Cooling control would use I2 MIN

 

 

or I2 RPM described later in this table.

 

 

 

MANRST

–100 to +100 (in % output)

MANUAL RESET—This parameter is only applicable if

 

[factory setting = 0]

control group parameter “CTRALG” is “PDMR”

 

 

(PD with manual reset). Because a proportional recorder

 

 

will not necessarily line out at setpoint, there will be a

 

 

deviation (offset) from setpoint. This reset value can be

 

 

used to eliminate the offset and lets the PV line out at

 

 

setpoint. The controller output is the computed output

 

 

plus the value of MANRST.

 

 

 

 

 

102

DR4300 Circular Chart Recorder Product Manual

12/03

Page 114
Image 114
Honeywell DR4300 manual Min, Rpm