Troubleshooting and Pen Alignment of Recorder with Display

8.5.10 Troubleshooting Modbus Communications

Procedure

Table 8-14explains what to do if Modbus communications are not successful.

Table 8-14 Troubleshooting Modbus Communications

Step

What to do

How to do it or

 

 

where to find the instructions

 

 

 

1

Verify that communications are enabled.

Refer to Section 4 - Configuration, Startup, and

 

 

Operation of Recorder with Display.

 

 

 

2

Check that the configured baud rate is

Refer to Section 4 - Configuration, Startup, and

 

correct.

Operation of Recorder with Display.

 

 

 

3

Check that the device address is correct.

Refer to Section 4 - Configuration, Startup, and

 

Each address must be unique. A recorder

Operation of Recorder with Display.

 

with two pens must have a unique

 

 

address for each pen channel.

 

 

 

 

4

Check that the communication wires are

Refer to Section 2 - Installation.

 

properly connected to the J3 connector on

 

 

the communication printed circuir

 

 

assembly (PCA).

 

 

 

 

5

Verify that the communcation cable

Refer to Section 9 - Replacing Hardware

 

connects J2 on the communication PCA

Assemblies.

 

to J3 on the PCA for Pen 1. The PCA for

 

 

Pen 1 is on the right when facing the

 

 

recorder.

 

 

If communication is used for Pen 2,

 

 

another communication cable must

 

 

connect J1 on the communication PCA

 

 

with J3 on the PCA for Pen 2.

 

 

 

 

6

Replace the communication PCA.

Refer to the replacement pocedure in Section 9 -

 

 

Replacing Hardware Assemblies.

 

 

 

12/03

DR4300 Circular Chart Recorder Product Manual

187