9.TROUBLESHOOTING

9.1Error Messages and Diagnosis

When the inverter goes wrong, it operates as indicated below. Find the cause and take contermeasures.

Error Messages and Diagnosis

 

 

 

Symptom

 

 

 

 

 

 

 

 

 

 

 

How(NOTE1)toreset

 

 

Circuitbreaker(MCB)

Electromagneticcontactor(Mg)

Thermalrelay(THRY)

Display on the

Failurealarmrelay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

digital operator

 

Cause

 

 

 

 

 

 

 

 

 

 

Check

Countermeasure

 

 

 

(display on the

 

 

 

 

 

 

 

 

LCD of the

 

(explanation

 

 

 

 

 

 

remote operator)

 

of message)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E 0 1

Overcurrent detected

A

Check whether a load was

Do not change loads

 

 

 

 

by the AC CT while

 

changed rapidly.

rapidly.

 

 

 

( O C . D r i v e )

 

 

 

 

 

 

the motor was running

 

 

 

 

 

 

 

 

 

 

Check whether the output

 

 

 

 

 

at a constant speed

 

Check whether there is a

 

 

 

 

 

(overcurrent during

 

shorted output or ground

lines or motor is shorted.

 

 

 

 

 

operation)

 

fault.

 

 

 

 

 

 

 

 

 

 

 

 

 

E 0 2

Overcurrent detected

A

Check whether the speed

Set a longer deceleration

 

 

 

 

by the AC CT during

 

was decreased rapidly.

time.

 

 

 

( O C . D e c e l )

 

 

 

 

 

 

motor deceleration

 

 

 

 

 

 

 

 

 

 

Check whether the output

 

 

 

 

 

(overcurrent during

 

Check whether there is a

 

 

 

 

 

deceleration)

 

shorted output or ground

lines or motor is shorted.

 

 

 

 

 

 

 

fault.

 

 

 

 

 

 

 

 

 

 

 

 

 

E 0 3

Overcurrent detected

A

Check whether a load was

Do not change loads

 

 

 

 

by the AC CT during

 

changed rapidly.

rapidly.

 

 

 

( O C . A c c e l )

 

 

 

 

 

 

motor acceleration

 

 

 

 

 

 

 

 

 

 

Check whether the output

 

 

 

 

 

(overcurrent during

 

Check whether there is a

 

 

 

 

 

acceleration)

 

shorted output or ground

lines or motor is shorted.

 

 

 

 

 

 

 

fault.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check whether the start

Lower the start frequency.

 

 

 

 

 

 

 

frequency is too high.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check whether the torque

Lower the torque boost.

 

 

 

 

 

 

 

boost is too high.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check whether the motor is

Check the motor or loads.

 

 

 

 

 

 

 

locked.

 

 

 

 

 

 

 

 

 

 

 

 

 

E 0 5

Overloaded inverter

A

Check for an overload.

Lower the load ratio.

 

 

 

 

(operation under an

 

 

 

 

 

 

( O v e r . L )

 

 

 

Set an appropriate level.

 

 

 

 

overload)

 

Check whether the

 

 

 

 

 

 

 

 

 

 

 

 

 

electronic thermal level is

 

 

 

 

 

 

 

 

correct. (Check whether the

 

 

 

 

 

 

 

 

level has been changed.)

 

 

 

 

 

 

 

 

 

 

NOTE 1: How to reset

A: Stop the inverter. Then, connect the <RS> and <CM1> control terminals or press the STOP/RESET key on the operator.

B:Opeate the circuit breaker and electromagnetic contactor (turn the power on again).

C:Stop the inverter. Then, reset the thermal relay.

9-1

Page 74
Image 74
Hitachi J300U Series instruction manual Troubleshooting, Error Messages and Diagnosis