Symptom

 

 

Probable cause

Countermeasure

 

 

 

 

 

 

 

Overload

 

Is the

 

 

torque boost too high ?

Decrease the torque boost.

 

 

 

(Electronic

 

Do the

 

 

 

Reset the electronic thermal characteristics

 

electronic thermal characteristics

thermal

 

match the set characteristics of the

and level.

trip)

 

motor ?

 

 

 

(Low

 

 

 

 

 

 

frequency

 

 

 

 

 

 

zone)

 

 

 

 

 

 

 

 

 

 

 

 

 

The input

 

Is the input voltage high ?

Lower the input voltage.

voltage

 

Is the equipment stopped with the

Set a deceleration time which is a little longer.

trips.

 

inverter DC voltage increased after

Increase the AVR set value above the current

 

 

sudden deceleration ?

input voltage and lower the V gain by

 

 

 

 

 

 

the ratio.

 

 

 

 

 

 

 

9-8

Page 81
Image 81