Symptom

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit breaker(MCB)

Electromagnetic contactor (Mg)

Thermal relay(THRY)

Display on the

Failure alarm relay

 

How to reset

 

 

digital operator

Cause

 

 

 

 

Check

Countermeasure

(display on the

 

 

 

LCD of the

(explanation

 

 

remote operator)

of message)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

Check for an overload.

Lower the load ratio.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check whether the thermal

Set the thermal relay to an

 

 

 

 

 

 

 

relay is set to an appropriate

appropriate value.

 

 

 

 

 

 

 

value.

 

 

 

 

 

 

 

 

 

 

 

 

B

Check whether there is a

Remove the short or ground

 

 

 

 

 

 

 

short or ground fault in the

fault.

 

 

 

 

 

 

 

power supply.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check whether the MCB

Increase the MCB capacity.

 

 

 

 

 

 

 

capacity is sufficient.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check whether the inverter

Repair the inverter module or

 

 

 

 

 

 

 

module or converter module

converter module.

 

 

 

 

 

 

 

is defective.

 

 

 

 

 

 

 

 

 

 

 

 

Power outage

B

Check for a power outage.

Restore the power supply to

 

 

 

 

 

 

 

 

normal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check whether the MCB or

Replace the MCB or Mg.

 

 

 

 

 

 

 

Mg has a poor contact.

 

 

 

 

 

 

 

 

 

 

9-5