Symptom

Probable cause

Countermeasure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The rpm

 

 

After checking the wiring of

Replace the frequency setter.

of the

 

 

the frequency setter, the rpm still

 

 

 

 

 

 

motor

 

 

does not increase when the setter

 

 

 

 

 

 

will not

 

 

is turned.

 

 

 

 

 

 

 

 

 

 

increase.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are terminals 7 and CM1, terminal 6

Turn off terminal 7 and 6. (When the

 

 

 

 

 

 

 

 

and CM1 ON (Sink type)?

frequency and multistage speed are fixed at

 

 

 

 

 

 

 

 

 

 

 

 

a given frequency, the speed potentiometer

 

 

 

 

 

 

 

 

 

 

 

 

will be invalid.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the load too great?

Decrease the load.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When the load is too great, the limiting

 

 

 

 

 

 

 

 

 

 

 

 

function will be activated, so that

 

 

 

 

 

 

 

 

 

 

 

 

the rotational speed will be lower than

 

 

 

 

 

 

 

 

 

 

 

 

the setting.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The rpm

 

 

Is the maximum frequency setting

Check the speed-change ratio.

of the

 

 

correct?

 

 

 

 

 

 

 

 

 

 

motor

 

 

Are the number of motor poles,

 

 

 

 

 

 

does not

 

 

the gear ratio, and pulley ratio correct?

 

 

 

 

 

 

match the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inverter.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The data

The data is

The STN terminal is turned ON and the

Turn the STN terminal OFF.

 

 

 

is

returned to

power is turned on.

 

 

 

 

Input the data again.

 

 

 

incorrect.

the initial

The input terminals 1 to 5 are turned

Replace the logic PCB.

 

 

 

 

 

setting.

ON and then power is turned on.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The data has

Was the power turned off without

Input the data and push the

 

 

 

 

FUNC

key once.

 

 

not changed.

pushing the

 

 

 

key after the data

 

 

 

 

 

 

 

 

FUNC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

was changed with

 

 

 

 

 

keys.

 

 

 

 

 

 

 

 

 

 

1

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The data is memorized upon power off.

Take six seconds or more when turning power

 

 

 

 

Is the time from power OFF to ON less

OFF and ON after changing the data.

 

 

 

 

than six seconds?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data copied

Is the power turned off for five seconds

Copy again and turn the power off five

 

 

by the copy

or more after the display changed

seconds or more after copying.

 

 

unit

from REMT to INV.

 

 

 

 

 

 

 

 

 

 

 

 

is not input.

(HRW-OJ)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The data

Frequency

The change of the terminal mode and

Confirm the change in

 

 

 

setting mode.

 

 

 

is not

setting can

digital operator mode were correct?

 

 

 

 

 

 

changed.

not be

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

changed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Run and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

stop can not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

be done.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The data can

Is the input terminal SFT ON ?

Turn the SFT terminal OFF.

 

 

 

 

 

not be

Is the software lock mode set at MD2

Turn the switch OFF.

 

 

 

 

 

changed.

or MD3 ?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: If software lock is ON because of

 

 

 

 

 

 

 

 

 

 

use with an explosion proof motor,

 

 

 

 

 

 

 

 

 

 

do not release the software locks.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9-7