Running method by autotuning data

When running the inverter using the autotuning data:

1.A-0 : The control method is set at SLV (sensorless vector control).

2.A-98 : The motor data is set on the autotuning side by the software switch. Make the above two settings.

NOTE: When no torque is outputted during the sensorless vector run after the above settings are made, make the following settings. Increase the set value of R1 of each remote operator (motor constant) before starting running.

[Setting method]

(1) Digital operator

 

 

 

FUNC

A

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FUNC

A

0

 

 

 

 

 

 

 

 

 

FUNC

A

98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FUNC

A

98

 

 

 

 

 

 

0

 

× 4

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

00

 

× 2

 

 

 

 

 

 

02

 

 

 

 

1. Select

 

4

(sensorless vector control) by

 

 

 

 

 

 

the

 

 

 

 

control method.

0:Constant torque characteristic

1:Reduced torque characteristic (1.5 power)

2:Reduced torque characteristic (1.7 power)

3:Reduced torque characteristic (2.0 power)

4:Sensorless vector control

2.Set the motor constant data to the data which is

A 9 8 measured by the autotuning function

using the software switch.

(Refer to the [A98] software switch of the opera-

tion manual.)

(When executing the second setting, change the switch.)

(2) Remote operator

 

 

F-04

 

CONTROL

 

 

 

 

 

FUNC

 

 

 

 

Initial display

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL

 

VC

 

 

 

 

 

× 4

 

 

 

 

 

 

 

 

CONTROL

 

SLV

 

 

 

 

 

STR

 

Initial display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX

DATA

NOR

 

 

 

 

 

× 2

 

 

× 2

 

 

 

 

 

 

 

 

 

 

STR

AUX

DATA

AUT

 

 

 

MON

 

 

 

 

 

 

By the above two settings, running by the autotuning data is available.

1.Select [SLV] (sensorless vector control) by the F-04 control method.

VC: Constant torque characteristic

VP1: Reduced torque characteristic (1.5 power)

VP2: Reduced torque characteristic (1.7 power)

VP3: Reduced torque characteristic (2.0 power)

SLV: Sensorless vector control

2.Set the [AUT] autotuning data by motor data selection of the F-05 motor constant.

By the above two settings, running by the autotuning data is available.

FS050.00000.00Hz

A-5