Symptom

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit breaker(MCB)

Electromagnetic contactor (Mg)

Thermal relay(THRY)

Display on the

Failure alarm relay

 

How to reset

 

 

digital operator

Cause

 

 

 

 

 

Check

Countermeasure

(display on the

 

 

 

LCD of the

(explanation

 

 

remote operator)

of message)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E 3 3

(NOTE 1)

A

Check whether the speed was

Set a longer acceleration

 

 

 

 

Failure detected by a

 

increased rapidly.

time.

 

 

 

( P M . A c c e l )

 

 

 

 

 

 

detector in the power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

module during motor

 

Check whether a load was

Do not change loads rapidly.

 

 

 

 

 

 

acceleration, or

 

changed rapidly.

 

 

 

 

 

 

 

excessive temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rise in the inverter

 

Check whether there is a shorted

Check whether the output

 

 

 

 

 

 

 

 

output or ground fault.

lines or motor is shorted.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check whether the start

Lower the start frequency.

 

 

 

 

 

 

 

 

frequency is too high.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check whether the torque

Lower the torque boost.

 

 

 

 

 

 

 

 

boost is too high.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check whether the motor is

Check the motor or loads.

 

 

 

 

 

 

 

 

locked.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E 3 4

(NOTE 1)

A

Check whether the

Check the installation.

 

 

 

 

Failure detected by a

 

installation is vertical and the

 

 

 

 

( P M . E R R )

 

 

 

 

 

 

 

detector in the power

 

wall is a nonflammable wall

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

module while the motor

 

such as an iron plate.

 

 

 

 

 

 

 

was stopping, or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

excessive temperature

 

Check whether the cooling fan

Replace the cooling fan.

 

 

 

 

 

 

rise in the inverter

 

is running and the ambient

 

 

 

 

 

 

 

 

 

temperature is too high.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check the internal power

Repair the internal power

 

 

 

 

 

 

 

 

supply.

supply.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check the main devices.

Repair main devices.

 

 

 

 

 

 

 

 

 

 

 

 

E 6 0

Defective J-FB PC

A

Refer to the manual supplied

 

 

 

 

( O P 1

0 )

 

board

 

with the J-FB PC board.

 

 

 

 

 

 

 

 

 

 

 

 

to

 

 

 

 

 

 

 

 

 

E 6 7

 

 

 

 

 

 

 

 

( O P 1

7 )

 

 

 

 

 

 

 

 

E 7 0

Defective J-FB PC

A

Refer to the manual supplied

 

 

 

 

( O P 2

0 )

 

board

 

with the J-FB PC board.

 

 

 

 

 

 

 

 

 

 

 

 

to

 

 

 

 

 

 

 

 

 

E 7 7

 

 

 

 

 

 

 

 

( O P 2

7 )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE 1: The failures detectable in the power module are overcurrents, excessively hot main devices, and insufficient voltages from the gate circuit power supply.