Hitachi J300U Series Abnormal, Power off, AL0-AL1 open, Contact rating 250 VAC Resistor load

Models: J300U Series

1 145
Download 145 pages 53.04 Kb
Page 33
Image 33

Terminal symbol

H

O

OI

L

CM2

 

FA1

• 12

RUN

OTQ

11

 

 

 

AL0

AL1

AL2

Terminal name

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Description

Frequency command power

• Initialization of a voltage signal by an external command

terminal

is between 0 and 10 VDC. (Switching from 0 to 5V is executed

 

by A48.) When inputting 4 - 20 mA, turn the input terminal at

Frequency command

ON.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

O

OI

L

 

 

 

 

H

O

OI

L

 

 

 

H O OI L

terminal (voltage command)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

-

 

 

 

 

+ -

 

 

 

 

 

 

 

 

 

 

 

 

 

terminal (current command)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VRO

 

DC0 to 10 V

DC4 to 20 mV

Frequency command

 

(500 Ω to 2 kΩ)

 

 

DC0 to 5V

Input impedance 250 kΩ

 

 

 

 

 

 

 

 

 

 

 

 

 

Input impedance 30 kΩ

 

common terminal

When a current is inputted from between OI and L and the value is 4 mA,

 

the output frequency may 0.6 Hz. If this occurs, set a value more than the

 

frequency which is outputted by [A 4] start frequency setting.

 

(NOTE 2)

 

 

 

 

 

 

 

 

 

 

 

 

Common terminal 2

Common terminal for intelligent output terminal

Frequency arrival signal

When each operator is used, and arrival signal can be

 

outputted at an optional frequency.

Signal during run

The transistor output is turned ON during running.

 

(Outputted even during DC injection braking)

Over-torque signal

The transistor output is turned ON when the torque is more

 

than the set value.

 

 

 

 

 

 

 

 

 

 

 

 

 

The set value can be changed by the remote operator.

 

Use this function only under the sensor less vector control.

 

 

Normal: AL0-AL1 close

 

 

Abnormal, Power off:

AL2 AL1

AL0

AL0-AL1 open

 

 

Fault alarm terminal

 

 

 

Contact rating

 

 

250 VAC

2.5

A (Resistor load)

Min 100Vac

 

0.2 A (Cosø=0.4)

10 mA

30 VDC

3.0

A (Resistor load)

5 VDC

 

0.7

A (cosø=0.4)

100 mA

NOTE 1: To set four or more multispeeds, use the CF3 terminal.

NOTE 2: When an inconvernience occurs in the above characteristics, adjust it using

and . The sum of both analog input signals is outputted

When selecting one of analog input current and voltage, make sure that the other is not inputted.

5-13