Hitachi J300U Series instruction manual 12-8

Models: J300U Series

1 145
Download 145 pages 53.04 Kb
Page 99
Image 99

 

Display

(Function mode 1)

(Function mode 2)

 

Setting, change

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

Function

Initialization display

Initialization

Setting contents

 

 

sequence

contents

 

 

No.

name

contents

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

F-20

DC braking

DCB SW

 

 

OFF

OFF

ON/OFF

• DC braking

 

 

 

DC

selection

 

 

 

 

 

 

 

 

 

 

 

 

ON: DC braking available

 

 

 

injection

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF: DC braking unavailable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

braking

DC braking

DCB KIND

 

LVL

LVL

LVL/EDG

• DC braking method selection

 

 

 

 

type

 

 

 

 

 

 

 

 

 

 

 

 

LVL: Level operation

 

 

 

 

selection

 

 

 

 

 

 

 

 

 

 

 

 

EDG: Edge operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC braking

DCB F

 

0000.5 Hz

0.5 Hz

0 to 400.0 Hz

• The frequency at which the

 

 

 

 

frequency

 

 

 

 

 

 

 

 

 

 

 

 

DC braking starts is set.

 

 

 

 

selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC braking

DCB V-STA

 

00

0

0 to 20

 

• The DC braking force at start

 

 

 

 

force selec-

 

 

 

 

 

 

 

 

 

 

 

 

is set.

 

 

 

 

tion (at start)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC braking

DCB V-STP

 

00

0

0 to 20

 

• The DC braking force at stop

 

 

 

 

force selec-

 

 

 

 

 

 

 

 

 

 

 

 

is set.

 

 

 

 

tion (at stop)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC braking

DCB T-STA

 

000.0 s

0 s

0 to 600.0

• The DC braking time at start

 

 

 

 

time selec-

 

 

 

 

 

 

 

 

 

 

 

 

is set.

 

 

 

 

tion (at start)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC braking

DCB T-STP

 

000.0 s

0 s

0 to 600.0

• The DC braking time at stop

 

 

 

 

time selec-

 

 

 

 

 

 

 

 

 

 

 

 

is set.

 

 

 

 

tion (at stop)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC braking

DCB STOP-T

0.00 s

0 s

0 to 5.00

The output frequency is

 

 

 

 

output cut-

 

 

 

 

 

 

 

 

 

 

 

 

lowered to the DC braking

 

 

 

 

off time

 

 

 

 

 

 

 

 

 

 

 

 

frequency and the free run

 

 

 

 

 

adjustment

 

 

 

 

 

 

 

 

 

 

 

time during execution of DC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

braking is set.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

F-21

Dynamic

BRD-%ED

001.5%

1.5%

0 to 100.0

• The allowable usage ratio of

 

 

 

 

braking

 

 

 

 

 

 

 

 

 

 

 

 

the braking resistor for 100

 

 

 

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

seconds is set. (NOTE 1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

F-22

Allowable

IPS TIME

 

 

1.0 s

1.0 s

0.3 to 25 s

• When an instantaneous power

 

 

 

The

instantaneous

 

 

 

 

 

 

 

 

 

 

 

 

failure occurs, the allowable

 

 

 

allowable

powerfailure

 

 

 

 

 

 

 

 

 

 

 

 

time until the power failure is

 

 

 

usage

time setting

 

 

 

 

 

 

 

 

 

 

 

 

recovered is set.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ratio of

Reclosing

IPS WAIT

 

 

001.0 s

1.0 s

0.3 to 100.0 s

• The waiting time until the

 

 

 

the

standbyafter

 

 

 

 

 

 

 

 

 

 

 

 

rerunning starts after an

 

 

 

braking

instantaneous

 

 

 

 

 

 

 

 

 

 

 

 

instantaneous power failure

 

 

 

resistor

powerfailure

 

 

 

 

 

 

 

 

 

 

 

 

occurs and is recovered is set.

 

 

 

for 100

recovered

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

seconds

Instantaneous

IPS POWR

 

ALM

ALM

ALM/FTP/

ALM: Alarm output

 

 

 

is set.

powerfailure

 

 

 

 

 

 

RST/ZST

ZST: 0 Hz start retry

 

 

 

 

restart

 

 

 

 

 

 

 

 

 

 

 

 

FTP: Retry after frequency

 

 

 

 

selection

 

 

 

 

 

 

 

 

 

 

 

 

matching is stopped

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RST: Rerunning start retry

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tripselection

IPS TRIP

 

 

OFF

OFF

ON/OFF

When an instantaneous power

 

 

 

 

during stop

 

 

 

 

 

 

 

 

 

 

 

 

failure occurs:

 

 

 

 

atunder

 

 

 

 

 

 

 

 

 

 

 

 

ON: Trip

 

 

 

 

voltage

 

 

 

 

 

 

 

 

 

 

 

 

OFF: Non-trip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

F-23

Electronic

E-THM CHAR

SUB

SUB

CRT/SUB/FRE

• Electronicthermalcharacteris-

 

 

 

Electronic

thermal

 

 

 

 

 

 

 

 

 

 

 

 

tic setting CRT: Constant

 

 

 

thermal

characteristic

 

 

 

 

 

 

 

 

 

 

 

 

torque characteristic

 

 

 

 

selection

 

 

 

 

 

 

 

 

 

 

 

 

SUB: Reduced torque charac-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

teristic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRE: Free characteristic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electronic

E-THM LEVEL

100%

100%

20 to 120%

 

 

 

 

 

thermallevel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE 1: Initial setting of usage ratio

1.5%

 

055-075L/HF

0%

 

 

 

 

110-550L/HF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12-8

Page 99
Image 99
Hitachi J300U Series instruction manual 12-8