12.4Protection function display list when the remote operator is used

There are protection functions for overcurrent, overvoltage, and undervoltage provided to protect the inverter. When one of the functions is performed, the output is cut off, and the motor is put into the free run state, and the status is kept until the inverter is forced to reset.

 

 

Remote operator(DOP)

Name

Digital operator display

copy unit(DRW)display

 

 

ERR1 ✽ ✽ ✽ ✽

 

Constant speed

OC.Drive

Overcurrent

Deceleration

OC.Decel

protection

 

 

 

Acceleration

OC.Accel

Overload

 

Over.L

protection

 

 

 

Braking resistor

 

OL.BRD

overload

 

 

 

Overvoltage

 

Over.V

protection

 

 

 

EEPROM error

 

EEPROM

Undervoltage

 

Under.V

protection

 

 

 

CT error

 

CT

CPU error

 

CPU

External trip

 

EXTERNAL

USP error

 

USP

Ground fault

 

GND.Flt

protection

 

 

 

Other displays

 

 

Remote operator(DOP)

Name

Digital operator display

copy unit(DRW)display

 

 

ERR1 ✽ ✽ ✽ ✽

Input overvoltage

 

OV.SRC

Instantaneous

 

Inst.P-F

power failure

 

 

 

Option connec-

Option 1

NG.OP1

 

 

tion error

Option 2

NG.OP2

 

Option PCB

Option 1

OP1

error

 

 

(NOTE 2)

Option 2

OP2

Phase failure

(NOTE 1)

PH.Fail

protection error

 

 

 

Constant speed

PM.Drive

Power module

Deceleration

PM.Decel

protection

Acceleration

PM.Accel

 

 

Stop

PM.ERR

Undervoltage

 

UV.WAIT

standby

 

 

 

For error contents, see page 8-1.

 

 

Display

Cause

Description

 

 

 

 

 

Communication error

This is displayed when an error occurs between the inverter and remote operator.

 

 

 

 

*=1. Protocol error

When the STOP key or another key is pressed, the original display appears.

 

R-ERROR COMM<>

 

 

 

=2. Time-out error

When the original display does not appear, turn the power off and then on once

 

 

 

 

 

 

 

 

 

again. Check whether any connectors are loose.

 

 

 

 

 

 

 

 

 

 

 

During inverter running

If one of the displays on the left occurs when the copy unit is used to read or copy,

 

R-ERROR INV.RUN

 

 

 

take the corresponding countermeasure.

 

 

 

 

 

 

 

 

 

 

 

 

• INV. RUN: Stop the running.

 

 

 

 

 

 

 

 

R-ERROR INV.TRIP

 

Under inverter trip

 

 

 

• INV. TRIP: Press the STOP key to release the trip.

 

 

 

 

 

 

• INV. TYPE: The inverter type of the copy source is different from that of the

 

 

 

 

Inverter type mismatch

 

R-ERROR INV.TYPE

 

copy destination. Use the same type of inverter to read or copy.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter read lock

The fourth switch of the DIP switch on the back of the remote operator is ON.

 

R-ERROR RD LOCK

 

 

 

When reading data, turn the switch OFF.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Instantaneous power

This indicates that the instantaneous power failure restart function is being performed.

 

RESTART

✽ ✽ ✽ .s

 

 

 

 

 

failure restart function in

• RESTART: 0 start is in execution.

 

 

 

 

 

 

 

ADJUST

✽ ✽ ✽ .s

 

operation

• ADJUST: Frequency matching is in execution.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Undervoltage

The supply voltage is lowered to the undervoltage level. When this display

 

UV WAIT

 

 

 

 

 

appears, turn the power on once again.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power OFF

The undervoltage after the power is turned off is displayed.

 

 

POWER OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This is displayed after the autotuning measurement is finished.

 

 

Tuning OK

 

 

Autotuning function end

 

 

 

 

 

• Tuning OK: The measurement terminates normally.

 

 

 

 

 

display

 

 

Tuning NG

 

 

• Tuning NG: The measurement fails.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE 1: Power OFF during motor deceleration may cause an input phase failure error.

 

 

NOTE 2: When the J-FB is installed, an error is display for each factor as shown below.

 

 

 

 

 

 

Digital operator

DOP, DRW

 

 

 

 

 

display

 

Encoder line break: Overspeed: Positioning error: Thermistor line break: Motor overheat:

Malfunction or abnormality on built-in CPU of the option:

12-16