Hitachi J300U Series instruction manual Ground fault on

Models: J300U Series

1 145
Download 145 pages 53.04 Kb
Page 76
Image 76

 

 

 

Symptom

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit breaker(MCB)

Electromagnetic contactor (Mg)

Thermal relay(THRY)

Display on the

Failure alarm relay

 

How to reset

 

 

digital operator

Cause

 

 

 

 

Check

Countermeasure

(display on the

 

 

 

LCD of the

(explanation

 

 

remote operator)

of message)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E 1 4

Ground fault on the

A

Check the wiring between the

Correct the portions having

 

 

 

 

output side of the

 

inverter and motor and also

a ground fault.

 

 

 

( G N D . F l t )

 

 

 

 

 

 

inverter

 

check the motor for a ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fault. (Use a megger.)

 

 

 

 

 

 

 

 

 

 

 

 

 

E 1 5

Excessive received

A

Check whether an

• Lower the voltage to be

 

 

 

 

voltage

 

excessive voltage was

received.

 

 

 

( O V . S R C )

 

 

 

 

 

 

 

 

received during an

• Reduces fluctuations of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation other than

the received voltage.

 

 

 

 

 

 

 

deceleration.

• Install an AC reactor on

 

 

 

 

 

 

 

 

the input side.

 

 

 

 

 

 

 

 

 

 

 

 

E 1 6

Defective power

A

Check whether the voltage

Restore the power supply

 

 

 

 

supply (instantaneous

 

is lowered.

to normal.

 

 

 

( I n s t . P - F )

 

 

 

 

 

 

power outage)

 

 

 

 

 

 

 

 

 

Check whether the MCB or

Replace the MCB or Mg.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mg has a poor contact.

 

 

 

 

 

 

 

 

 

 

 

 

 

E 1 7

Incorrectly connected

A

Check the connectors and

Repair the defective

 

 

 

 

option-1 PC board

 

other connections for

connections.

 

 

 

( N G . O P 1 )

 

 

 

 

 

 

 

 

abnormal conditions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E 1 8

Incorrectly connected

A

Check the connectors and

Repair the defective

 

 

 

 

option-2 PC board

 

other connections for

connections.

 

 

 

( N G . O P 2 )

 

 

 

 

 

 

 

 

abnormal conditions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E 1 9

Defective option-1 PC

A

Refer to the instruction

 

 

 

 

( O P 1 )

 

board

 

manual.

 

 

 

 

 

 

 

 

 

 

 

 

 

E 2 0

Defective option-2 PC

A

Refer to the instruction

 

 

 

 

( O P 2 )

 

board

 

manual.

 

 

 

 

 

 

 

 

 

 

 

 

 

E 2 4

Defective power

A

Check the power supply

Repair the abnormal

 

 

 

 

supply (missing phase)

 

connections for abnormal

portions.

 

 

 

( P H . F a i l )

 

 

 

 

 

 

 

 

conditions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check whether the MCB or

Replace the MCB or Mg.

 

 

 

 

 

 

 

Mg has a poor contact.

 

 

 

 

 

 

 

 

 

 

 

 

 

E 3 1

(NOTE 1) Failure detected

A

Check whether a load was

Do not change loads

 

 

 

 

by a detector in the power

 

changed rapidly.

rapidly.

 

 

 

( P M . D r i v e )

 

 

 

 

 

 

module while the motor

 

 

 

 

 

 

 

 

 

Check whether there is a

Check whether the output

 

 

 

 

 

was running at a constant

 

 

 

 

 

 

speed, or excessive tem-

 

shorted output or ground

lines or motor is shorted.

 

 

 

 

 

perature rise in the inverter

 

fault.

 

 

 

 

 

 

 

 

 

 

 

 

 

E 3 2

(NOTE 1) Failure detected

A

Check whether the speed

Set a longer deceleration

 

 

 

 

by a detector in the power

 

was decreased rapidly.

time.

 

 

 

( P M . D e c e l )

 

 

 

 

 

 

module during motor

 

 

 

 

 

 

 

 

 

Check whether there is a

Check whether the output

 

 

 

 

 

deceleration, or excessive

 

 

 

 

 

 

temperature rise in the

 

shorted output or ground

lines or motor is shorted.

 

 

 

 

 

inverter

 

fault.

 

 

 

 

 

 

 

 

 

 

NOTE 1: The failures detectable in the power module are overcurrents, excessively hot main devices, and insufficient voltages from the gate circuit power supply.

9-3

Page 76
Image 76
Hitachi J300U Series instruction manual Ground fault on