8 V 10 V Frequency
4 V 5V command
16.8 20mA
10 V Frequency
5 V command
20 mA

Extension

function

code

Contents and display

Set the frequency for starting output for an external frequency command (0 to 10 V, 0 to 5 V,

4 to 20 mA) and the frequency for ending output. When 0 Hz is set, this function will be canceled.

External frequency setting start

External Frequency setting end

External frequency

Initial value

setting start

.

(Hz)

60

Setting method

50

frequencyOutput

 

 

 

 

 

FUNC

2

1

30

 

 

 

 

 

 

FUNC

(400)

0

 

 

 

 

 

0

External frequency

 

 

4

 

Output

 

setting end

 

60

 

frequency

Same as A26

(Hz)

 

 

 

0

2

0

1

4

7.2

Start setting command (20%)

NOTE 1: The standard setting is 0 Hz. In this case, the selected V/f pattern is used for running.

NOTE 2: When changing the V/f pattern after A 26 (start) and A 27 (end) are set, readjust A 26 (start) and A 27 (end).

NOTE 3: When A 26 (start) > A 27 (end) is set and the frequency command value is minimized (0 V or 4 mA),

the output frequency may be

lowered than the value which is set by A 26 by 0.1 to 0.3 Hz. The reason is that it is judged that there is some frequency due to noise on the signal line and it is a normal operation.

NOTE 4: The setting shown left is also possible with F31 of the remote operator.

End setting command (80%)

Instanta- neous restart selection

Set the inverter retry method when a power error occurs. Select the set value of the retry method to be used.

Initial value

Setting method

 

 

2

1

 

 

 

 

 

 

FUNC

Initial value

FUNC

 

 

 

 

Set value

Function

0Alarm output after tripped

1Deceleration stop at the time

of restart

2

Frequency matching start at the time

of restart ( Note 1)

 

 

 

3

0 Hz start at the time of restart

Restart selection

NOTE 1: When the base frequency is one of the following ones, frequency matching may restart at 0 Hz. When the base frequency is 60 Hz: Driven at 40 Hz or less

When the base frequency is 50 Hz: Driven at 30 Hz or less

For other precautions, refer to Chapter 1, "Instantaneous stop restart" of Appendix 2.

NOTE 2: Since the retry mode is selected, the equipment restarts for trips of overcurrent, overvoltage, or undervoltage. For undervoltage, 16 retries (17th trip) are executed.

For overcurrent or overvoltage, 3 retries (fourth trip) are executed.

Do not use this function for a case that a fallen substance should be held by the machine brake when the motor is in the free-run mode.

7-20