Hitachi J300U Series instruction manual Inverter

Models: J300U Series

1 145
Download 145 pages 53.04 Kb
Page 29
Image 29

R

S

T

 

(L1) (L2) (L3)

 

 

 

(+) P

 

 

Inverter

 

 

 

 

RB

 

(T1) (T2) (T3)

 

U

V

W

 

 

 

 

 

 

 

Thermal relay

Motor

IM

Part description

Function

AC reactor for

This part is used when the unbalance voltage ratio is 3%

improving

 

or more and power supply is 500 kVA or more, and there

the power factor

is a rapid change in the power supply.

(ALI-

L)

It also improves the power factor.

(ALI-

H)

 

 

 

Radio noise filter

Using the inverter may cause noise on the peripheral

(Zero phase

equipment through the power lines.

reactor) (ZCL-A)

This part reduces noise.

 

 

EMI filter for

This part reduces common noise generated between

inverter

 

the power supply and the ground, as well as normal noise.

(FFJ300-

)

Put it in the primary side of inverter.

 

 

Regenerative

This part is used for applications that needs to increase

resistor

 

the brake torque of the inverter or to frequently turn on

(RB

- )

and off and to run high inertia load.

 

 

Radio noise filter

This part reduces noise generated at the output of

(Zero phase

the inverter.

reactor) (ZCL-A)

(It is possible to use for both input and output.)

 

 

AC reactor for

Running motors with the inverter generates vibration

reducing vibration

greater than that with commercial power supply.

(ACL-L-

)

This part installed between the inverter and motor reduces

(ACL-H-

)

torque ripple.

 

 

When the cable length between the inverter and motor is

 

 

long, a countermeasure for a malfunction of the termal

 

 

relay is taken.

 

 

 

NOTE 1: The applicable equipment is for Hitachi standard four pole squirrel-cage motor

NOTE 2: Be sure to consider the capacity of the circuit breaker to be used.

NOTE 3: Be sure to use bigger wires for power lines if the distance exceeds 20m.

NOTE 4: Be sure to use an grounding wire same size of power line or similar.

(*)Use AWG 16 wire for the alarm signal wire.

Classify the detective current of the earth leakage breaker depending on the total distance between the inverter and the motor.

length

Detective current (mA)

100 m and less

30

300 m and less

100

600 m and less

200

NOTE 5: When using CV wire and metal tube, the leakage current is around 30 mA/km.

NOTE 6: The leakage current becomes eight times because IV wires have a high dielectric constant. Therefore, use an one class larger earth leakage breaker according to the left table.

5-9

Page 29
Image 29
Hitachi J300U Series instruction manual Inverter