Mitsubishi Electronics FR-S500 Specification list 4.1.1 Ratings, Three-phase 200V power supply

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 180
Image 180
Specification list

Specification list

4.1 Specification list

4.1.1 Ratings

(1) Three-phase 200V power supply

Type FR-S520E- K-NA

 

0.1

0.2

 

0.4

0.75

 

1.5

 

2.2

3.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Applied motor capacity (*1)

 

kW

0.1

0.2

 

0.4

0.75

 

1.5

 

2.2

3.7

 

 

 

 

 

 

 

 

 

 

 

 

 

HP

1/8

1/4

 

1/2

1

 

2

 

3

5

 

 

 

 

 

 

Output

Rated capacity (kVA) (*2)

 

0.3

0.5

 

1.0

1.6

 

2.8

 

4.0

6.6

Rated current (A)

 

 

0.8

1.4

 

2.5

4.1

 

7.0

 

10

16.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overload current rating (*3)

 

150% 60s, 200% 0.5s (inverse time characteristics)

 

Voltage (*4)

 

 

 

Three-phase 200 to 240V

 

 

supply

Rated input AC voltage/frequency

 

Three-phase 200 to 240V 50Hz/60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Permissible AC voltage fluctuation

 

 

170 to 264V 50Hz/60Hz

 

 

 

 

 

 

 

Power

Permissible frequency fluctuation

 

 

 

Within ±5%

 

 

 

 

Power supply system capacity

0.4

0.7

 

1.2

2.1

 

4.0

 

5.5

9

 

 

 

 

 

(kVA) (*5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protective structure (JEM1030)

 

 

 

 

Enclosed type (IP20)

 

 

 

 

 

 

 

 

 

 

 

Cooling system

 

 

Self-cooling

 

 

Forced air cooling

Approximate mass (kg (lbs))

 

0.5

0.5

 

0.8

0.9

 

1.5

 

1.5

2.1

 

(1.1)

(1.1)

 

(1.76)

(1.98)

 

(3.3)

 

(3.3)

(4.62)

 

 

 

 

 

 

 

*1. The applied motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.

*2. The rated output capacity indicated assumes that the output voltage is 230V.

*3. The % value of the overload current rating indicates the ratio of the overload current to the inverter's rated output current.

For repeated duty, allow time for the inverter and motor to return to or below the temperatures under 100% load.

*4. The maximum output voltage does not exceed the power supply voltage. You can set the maximum output voltage to any value below the power supply voltage. However, the

pulse voltage value of the inverter output side voltage remains unchanged at about 2 that of the power supply.

*5. The power supply capacity changes with the values of the power supply side inverter impedances (including those of the input reactor and cables).

170