Additional function parameters

2.8 Additional function parameters

2.8.1Remote setting function selection (Pr. 59 )

If the operation panel is located away from the control box, you can use contact signals to perform continuous variable-speed operation, without using analog signals.

(Hz)

 

 

When Pr. 59="2"

 

 

 

When Pr. 59="1"

 

Output frequency

*

 

 

 

 

 

 

 

 

 

 

ON

 

ON

 

Acceleration(RH)

ON

 

 

 

Deceleration(RM)

ON

 

 

 

 

ON

 

 

Clear(RL)

 

 

 

Forward rotation

ON

ON

ON

ON

(STF)

ON

 

 

ON

Power supply

 

 

 

 

 

 

* External running frequency (other than multi-speed) or PU running frequency

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

59

Remote setting

0

0, 1, 2

Setting is enabled when Pr. 30 = "1"

function selection

 

 

 

 

REMARKS

•When the remote function is used, the output frequency of the inverter can be compensated

for as follows:

 

External operation mode

Frequency set by RH/RM operation plus external analog

 

frequency command

PU operation mode

Frequency set by RH/RM operation plus setting dial or PU

 

digital preset frequency

<Operation panel operation procedure>

 

 

 

 

 

 

 

 

Monitor, frequency

 

Turn the setting dial to

 

Press the SET to

 

setting mode MODE

 

make correction.

 

complete setting.*

 

 

 

 

 

 

*When you have set "1" in Pr. 53 "frequency setting operation selection", you need not press the SET .

2

FUNCTIONS

95

Page 105
Image 105
Mitsubishi Electronics FR-S500 instruction manual Additional function parameters, Remote setting function selection Pr