2.8 Additional function parameters

Additional function parameters

2.8 Additional function parameters

2.8.1Remote setting function selection (Pr. 59 2.8.1Remote setting function selection (Pr. 59 ))

If the operation panel is located away from the control box, you can use contact signals to perform continuous variable-speed operation, without using analog signals.

(Hz)

 

 

When Pr. 59="2"

 

 

 

When Pr. 59="1"

 

Output frequency

*

 

 

 

 

 

 

 

 

 

 

ON

 

ON

 

Acceleration(RH)

ON

 

 

 

Deceleration(RM)

ON

 

 

 

 

ON

 

 

Clear(RL)

 

 

 

Forward rotation

ON

ON

ON

ON

(STF)

ON

 

 

ON

Power supply

 

 

 

 

 

 

* External running frequency (other than multi-speed) or PU running frequency

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

59

Remote setting

0

0, 1, 2

Setting is enabled when Pr. 30 = "1"

function selection

 

 

 

 

REMARKS

•When the remote function is used, the output frequency of the inverter can be compensated

for as follows:

 

External operation mode

Frequency set by RH/RM operation plus external analog

 

frequency command

PU operation mode

Frequency set by RH/RM operation plus setting dial or PU

 

digital preset frequency

<Operation panel operation procedure>

 

 

 

 

 

 

 

 

Monitor, frequency

 

Turn the setting dial to

 

Press the SET to

 

setting mode MODE

 

make correction.

 

complete setting.*

 

 

 

 

 

 

*When you have set "1" in Pr. 53 "frequency setting operation selection", you need not press the SET .

2

FUNCTIONS

95

Page 105