*3. The power factor may be slightly lower.

Main circuit terminals

3) Single-phase 100V power input

Motor

 

No-fuse Breaker

Magnetic

Power Factor

Power Factor

 

(NFB *1, 4) or

Contactor

Improving AC

Improving DC

Output

Applied Inverter

Earth Leakage

(MC)

Reactor

Reactor

(kW

Type

Circuit Breaker

(Refer to

(Refer to page

(Refer to page

(HP))

 

(ELB) (Refer to

 

page 16)

17) (*3)

17) (*5)

 

 

page 12) (*2, 4)

 

 

 

 

 

0.1

FR-S510WE-0.1K-NA

30AF/10A

S-N10

FR-BAL-0.75K

(1/8)

0.2

FR-S510WE-0.2K-NA

30AF/15A

S-N10

FR-BAL-1.5K

(1/4)

0.4

FR-S510WE-0.4K-NA

30AF/20A

S-N20,

FR-BAL-2.2K

(1/2)

S-N21

0.75

FR-S510WE-0.75K-NA

30AF/30A

S-N20,

FR-BAL-3.7K

(1)

 

 

S-N21

 

 

*1. •Select the NFB according to the inverter power

 

 

 

IM

NFB

 

INV

supply capacity.

 

 

 

 

 

•Install one NFB per inverter.

 

 

 

IM

NFB

 

INV

 

 

 

*2. For installations in the United States or Canada, the circuit breaker must be inverse time or instantaneous trip type.

*3. The power factor may be slightly lower.

*4. When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the inverter, etc. Identify the cause of the trip, then remove the cause and power on the breaker.

*5. The single-phase 100V power input model does not allow the power factor improving DC reactor to be fitted.