*The value is nearly 100 (%) in the maximum position of the potentiometer.
8

Explanation of functions (parameters)

Changingexample Changing the calibration parameter C4 "frequency setting voltage gain" value

POINT

The calibration parameter C4 is an extended function parameter. Pr. 30 must be set to "1".

(2)Adjusting a deviation of the highest frequency from the Pr. 38 (Pr. 39) setting.

(2)-1 Making adjustment with a voltage applied directly across terminals 2-5 (with a current flowing across terminals 4-5)

OperationDisplay

1.Confirm the RUN indication and operation mode indication.

The inverter must be at a stop.

The inverter must be in the PU operation mode.

(Press the

PU

)

 

 

EXT

 

 

2. Press the MODE to choose the parameter

MODE

setting mode.

 

 

3. Turn the

to show "

".

 

Pr. 30 must be set to "1".

 

 

(For the Pr. 30 setting method, refer to

 

the instruction manual (basic).)

 

4. Press the SET

to show "

".

SET

When adjusting Pr. 38

 

 

5. Turn the

until the calibration

 

parameter C4 "frequency setting

 

voltage gain" appears.

 

 

6. Press the SET

to show the analog

SET

voltage value (%).

 

 

7. Apply a 5V voltage.

 

3 4 5 6 7

(Turn the external potentiometer

2

1

9

connected to across terminals 2-5 to

10

 

the maximum (any position).)

RUN

PU

EXT

The parameter number read previously appears.

Analog voltage value (%) across terminals 2-5

*

CAUTION

After performing operation in step 7, do not touch the until completion of calibration.

8. Press the SET to set the value.

*

SET

By turning the

Press the SET

Press the SET

Flicker ... Parameter setting complete!! (Adjustment complete)

*The value is nearly 100 (%) in the maximum position of the potentiometer.

, you can read another parameter.

to return to the

indication (step 4).

twice to show the next parameter ( ).

The frequency meter (indicator) connected to across terminals AM-5 does not indicate just 50Hz ... Why?

The calibration parameter C1 "AM terminal calibration" value must be set. (For the setting method, refer to the instruction manual (basic).)

When write is performed, an error ( ) is displayed.

The gain and bias frequency settings are too close.

84

Page 94
Image 94
Mitsubishi Electronics FR-S500 instruction manual Press the Mode to choose the parameter, Setting mode Turn To show