2.15 Communication parameters

You can perform communication operation from the RS-485 connector of the inverter through RS-485.

(1) Operational functions

1)Operation mode switching [Operation mode switching method]

 

 

Switching by

Switching by operation panel

 

 

 

 

 

 

computer program

/parameter unit (FR-PU04)

 

 

 

 

Computer

C

External

 

A

 

 

PU

 

 

 

 

 

 

 

 

 

 

 

 

link

 

 

 

 

 

 

 

 

 

 

operation

 

operation

 

operation

 

 

 

D

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

 

 

 

 

 

(Switching must not be made)

F

 

 

 

 

 

 

*1.

 

 

 

 

 

 

 

 

 

 

 

Symbol

Switching Type

 

 

Switching Method

 

 

 

 

A

PU operation to external

PU

of the operation panel or the

PU

/

EXT

of

operation

 

Using the EXT

 

 

the parameter unit (FR-PU04)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

External operation to PU

PU

of the operation panel or the

PU

/

EXT

of

operation

 

Using the EXT

 

 

the parameter unit (FR-PU04)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

External operation to

Using the

 

 

H0000: Communication

computer link operation

computer program

Read (H7B)/

operation

 

 

 

 

 

 

 

 

 

 

 

 

 

Write (HFB)

H0001: External

 

 

D

Computer link operation to

Using the

 

 

 

external operation

computer program

 

operation

 

 

 

 

 

 

 

 

 

 

E

PU operation to computer

Switching must not

be made

 

A and then

 

 

link operation

(External operation may be selected at

 

 

 

switched to computer link operation at

C *)

 

 

 

 

 

 

 

 

 

 

 

F

Computer link operation to

Switching must not be made

 

 

 

 

 

 

PU operation

(External operation may be selected at D and then

 

 

switched to PU operation at B *)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*When "1" is set in the communication parameter n10 "link startup mode selection", the inverter is placed in the computer link operation mode at power on or inverter reset. (Note that it is overridden by the Pr. 79 "operation mode selection" setting.)

REMARKS

Unlike the other inverters, the FR-S500 series is not the type of inverter whose operation panel is removed to make communication.

Parameter setting using setup S/W is not enabled in the PU operation mode and external / PU combined operation mode (Pr. 79 = 1, 3, 4). Also, pressing the RUN on the operation panel starts the inverter in the external / PU combined operation mode. (Pr. 79=1, 3)