Mitsubishi Electronics FR-S500 Connection of the high power factor converter FR-HC

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 49
Image 49
1.6.2Connection of the high power factor converter (FR-HC)

Connection to the Stand-Alone Option

1.6.2Connection of the high power factor converter (FR-HC)

When connecting the high power factor converter (FR-HC) to suppress power supply harmonics, perform wiring securely as shown below. Incorrect connection will damage the high power factor converter and inverter.

R

NFB

Power supply

S T

 

 

(Caution 2)

High power factor converter (FR-HC)

 

 

 

 

Inverter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MC1

MC2

R4

 

S4

T4

 

 

N

P

 

Y1 or Y2

RDY

RSO

SE

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

(Caution 2)

 

 

 

 

 

R4

S4

 

T4

 

 

 

 

 

 

 

 

 

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

From FR-HCL02

 

 

 

 

 

 

 

 

 

SD

(Caution 1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RES (Caution 4)

 

 

 

 

 

R3

S3

 

T3

 

 

 

 

 

 

 

 

 

MRS (Caution 4)

 

 

 

 

 

MC1MC2 External box

 

 

 

 

 

 

(Caution 5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R2

S2

 

T2

 

 

 

 

 

 

P

 

 

 

 

 

 

FR-HCL01

 

 

 

 

 

 

 

 

 

N (Caution 6)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

S

 

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Caution 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION

1.Use sink logic (factory setting) when the FR-HC is connected. The FR-HC cannot be connected when source logic is selected.

2.The power input terminals R, S, T must be open. Incorrect connection will damage the inverter. Opposite polarity of terminals N, P will damage the inverter.

3.The voltage phases of terminals R, S, T and terminals R4, S4, T4 must be matched before connection.

4.Use Pr. 60 to Pr. 63 (input terminal function selection) to assign the terminals used for the RES and MRS signals.

5.Do not insert NFB between terminals P-N (P - P, N - N)

6.The N terminal is not provided for the FR-S520E-0.1K to 0.75K.

1

WIRING

39

Page 49
Image 49
Mitsubishi Electronics FR-S500 instruction manual Connection of the high power factor converter FR-HC