Display function parameters

2.6.2Setting dial function selection (Pr. 53 )

You can use the dial like a potentiometer to perform operation.

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

 

 

 

 

 

0: Setting dial

 

 

Frequency setting

 

 

frequency setting

Setting is

53

0

0, 1

mode

enabled when

operation selection

 

 

 

1: Setting dial

Pr. 30 = "1"

 

 

 

 

 

 

 

 

potentiometer mode

 

Using the setting dial like a potentiometer to perform operation

POINT

•Set "1" (extended function parameter valid) in Pr. 30 "extended function display selection".

•Set "1" (setting dial potentiometer mode) in Pr. 53 "frequency setting operation selection".

Operation example Changing the frequency from 0Hz to 60Hz during operation

OperationDisplay

1.Mode/monitor check

Choose monitor/frequency monitor. ( MODE )

The inverter must be in the PU operation mode.

RUN

PU

EXT

(Press the EXTPU .)

Pr. 30 must be set to "1".

Pr. 53 must be set to "1".

2. Press the RUN to start the inverter.

3. Turn the clockwise until

RUN

RUN

PU

EXT

"60.0" appears. The flickering frequency is the set frequency.

You need not press the SET .

REMARKS

Flickers for 3s.

•If flickering "60.0" turns to "0.0", the Pr. 53 "frequency setting operation selection" setting may not be "1".

•Independently of whether the inverter is running or at a stop, the frequency can be set by merely turning the dial.

•When the frequency is changed, it will be stored as the set frequency after 10s.

2

FUNCTIONS

Refer to (page 90).