Calibration parameters

Changing example Deflecting the meter (analog indicator) to full-scale (5V) at the preset frequency of 60Hz (for frequency setting, refer to the instruction manual (basic).)

POINT

•The calibration parameters "C1" can be made to be ready by setting "1" (extended function parameter valid) in Pr. 30 "extended function display selection".

•Set the value of the calibration parameter C1 "AM terminal calibration".

OperationDisplay

Press the MODE to choose the parameter setting mode.

Turn the to show

" " .

Pr. 30 must be set to "1".

(For details, refer to the instruction manual (basic).)

Press the SET to show

" " .

The parameter number read

MODE

previously appears.

SET

Turn the until the calibration parameter C1 "AM terminal calibration" appears.

Press the SET to enable setting.

If the inverter is at a stop, press the RUN to start it. (The motor

need not be connected.)

7. Turn the

to adjust the

indicator needle to the

desired position.

8. Press the

SET .

Setting is complete.

SET

RUN

RUN

PU

EXT

+

Analog indicator

-

SET

Flicker ... Parameter setting complete!!

2

By turning the

, you can read another parameter.

 

Press the

SET

to return to the

indication (step 3).

 

Press the

SET

twice to show the next parameter (

).

REMARKS

•Depending on the set value, it may take some time for the needle to move.

•If "1" is set in Pr. 30 "extended function display selection", the calibration parameter C1 "AM terminal calibration" can also be set in the external operation mode.

•When the FR-PU04 is used, make calibration with Pr. 901.