Mitsubishi Electronics FR-S500 Restart operation parameters, Monitoring reference Pr. 55 , Pr

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 102
Image 102
2.6.3Monitoring reference (Pr. 55 , Pr. 56 )

Restart operation parameters

2.6.3Monitoring reference (Pr. 55 2.7 Restart operation parameters, Pr. 56 2.7.1Restart setting (Pr. 57 , Pr. 58 , H6 ))

Set the frequency or current which is referenced when the output frequency or output current is selected for the terminal AM.

5VDC (terminal AM)

Outputor display

 

Output

Pr.55

frequency

 

5VDC (terminal AM)

Outputor display

 

Output

Pr.56

frequency

 

Parameter

Name

Factory Setting

Setting

Remarks

Range

 

 

 

 

55

Frequency monitoring

60Hz

0 to 120Hz

 

reference

Setting is enabled when

 

 

 

 

 

 

 

Pr. 30 = "1"

56

Current monitoring

Rated output

0 to 50A

reference

current

 

 

 

 

<Setting>

Refer to the above diagrams and set the frequency monitoring reference value in Pr. 55 and the current monitoring reference value in Pr. 56.

Pr. 55 is set when Pr. 54 "AM terminal function selection" = "0" and Pr. 56 is set when Pr. 54 = "1".

In Pr. 55 and Pr. 56, set the frequency and current at which the output voltage of terminal AM will be 5V.

CAUTION

The maximum output voltage of terminal AM is 5VDC.

2.7 Restart operation parameters

2.7.1Restart setting (Pr. 57 Manual background, Pr. 58 Manual background, H6 Manual background)

At power restoration after an instantaneous power failure, you can restart the inverter without stopping the motor (with the motor coasting).

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

57

Restart coasting time

- - -

0 to 5s,

 

- - -

 

 

 

 

 

58

Restart cushion time

1s

0 to 60s Setting is enabled when Pr. 30 = "1"

 

Automatic restart after

 

 

 

H6 (162)

instantaneous power

1

0, 1, 10

 

 

failure selection

 

 

 

The parameter number in parentheses is the one for use with the parameter unit (FR-PU04).