Mitsubishi Electronics FR-S500 instruction manual Input filter time constant Pr, Setting

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 115
Image 115
2.10.4 Input filter time constant (Pr. 74 )

Operation selection function parameters

2.10.4 Input filter time constant (Pr. 74 2.10.5 Reset selection/PU stop selection (Pr. 75 ))

You can set the input section's built-in filter constant for an external voltage or current frequency setting signal.

Manual background Effective for eliminating noise in the frequency setting circuit.

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

74

Input filter time

1

0 to 8

Setting is enabled when Pr. 30 = "1"

constant

 

 

 

 

<Setting>

Increase the filter time constant if steady operation cannot be performed due to noise. A larger setting results in slower response. (The time constant can be set between approximately 1ms to 1s with the setting of 0 to 8. A larger setting results in a larger filter time constant.)

2.10.5 Reset selection/PU stop selection (Pr. 75 Manual background)

 

You can make reset input acceptance selection and choose the stop function

 

 

from the operation panel (PU).

 

 

 

 

 

Reset selection :You can choose the reset function input (RES signal) timing.

 

PU stop selection :When an alarm etc. occurs in any operation mode, you can

 

 

 

make a stop from the operation panel by pressing the

STOP .

 

 

 

 

 

 

 

 

RESET

 

 

 

 

 

 

 

 

 

 

Parameter

Name

Factory

 

Setting

Remarks

 

 

Setting

 

Range

 

 

 

 

 

 

 

 

 

75

 

Reset selection/

14

0, 1, 14, 15

Setting is enabled when Pr. 30 = "1"

 

 

PU stop selection

 

 

 

 

 

 

 

 

 

<Setting>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr. 75

 

Reset Selection

 

 

PU Stop Selection

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

0

Reset input normally enabled.

 

The PU stop key is invalid. Note that the

RESETSTOP is

 

 

Enabled only when the protective

 

 

1

 

valid only in the PU operation mode or combined

 

 

function is activated.

 

 

operation mode (Pr. 79 = "4").

 

 

 

 

 

 

 

 

 

14

Reset input normally enabled.

 

Pressing the RESETSTOP decelerates the inverter to a

 

 

Enabled only when the protective

 

 

15

 

stop in any of the PU, external and communication

 

 

function is activated.

 

 

operation modes.

 

 

 

 

 

 

 

 

2

FUNCTIONS

105

Page 115
Image 115
Mitsubishi Electronics FR-S500 Input filter time constant Pr, Reset selection/PU stop selection Pr, Setting