Standardconnection diagramand terminal specifications

￿Single-phase 100V power input

NFB

MC

 

Motor

Power

 

 

R/L1

U

 

supply

S/L2

V

IM

 

 

W

 

 

 

 

Ground

REMARKS

To ensure safety, connect the power input to the inverter via a magnetic contactor and earth leakage circuit breaker or no-fuse breaker, and use the magnetic contactor to switch power on-off.

The output is three-phase 200V.

1.1.2Explanation of main circuit terminals

(1) Main circuit

Terminal

Terminal Name

Description

Symbol

 

 

R/L1, S/L2,

AC power input

Connect to the commercial power supply.

T/L3 (*1)

 

 

U, V, W

Inverter output

Connect a three-phase squirrel-cage motor.

PR (*2)

 

Do not use PR terminal.

 

 

 

 

 

Brake unit

Connect the brake unit (BU), power regeneration

P/+, N/

common converter (FR-CV) or high power factor

connection

converter (FR-HC). (The N/- terminal is not provided for

 

 

 

 

 

 

 

 

 

 

 

the FR-S520E-0.1K to 0.75K-NA.)

 

 

 

 

 

 

 

 

 

 

 

 

Power factor

Remove the jumper across terminals P - P1 and connect

 

 

 

 

 

the optional power factor improving DC reactor (FR-

P/+, P1

improving DC

reactor

BEL(-H)).

 

 

 

 

 

(The single-phase 100V power input model cannot be

 

 

 

 

 

connection

 

 

 

 

 

connected.)

 

 

 

 

 

 

 

 

 

 

 

 

Ground

For grounding the inverter chassis. Must be grounded.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*1. When using single-phase power input, terminals are R/L1 and S/L2.

*2. The PR terminal is provided for the FR-S520E-0.4K to 3.7K-NA.