Mitsubishi Electronics FR-S500 instruction manual Troubleshooting, Motor remains stopped

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 176
Image 176
3.2 Troubleshooting

Troubleshooting

3.2 Troubleshooting

POINTS

If the cause is still unknown after every check, it is recommended to initialize the parameters (return to factory setting) then re-set the required parameter values and check again.

3.2.1 Motor remains stopped

3.2.1 Motor remains stopped 1) Check the main circuit

Check that a proper power supply voltage is applied (operation panel display is provided).

Check that the motor is connected properly. Check that the jumper across P - P1 is connected.

Manual background 2) Check the input signals

Check that the start signal is input.

Check that both the forward and reverse rotation start signals are not input simultaneously.

Check that the frequency setting signal is not zero.

Check that the AU signal is on when the frequency setting signal is 4 to 20mA.

Check that the output stop signal (MRS) or reset signal (RES) is not on. (Assign signals MRS and RES using Pr. 60 to Pr. 63 (input terminal function selection).)

Check that the sink or source jumper connector is fitted securely. Manual background 3) Check the parameter settings

Check that the reverse rotation prevention (Pr. 78) is not selected. Check that the operation mode (Pr. 79) setting is correct.

Check that the bias and gain (C2 to C7) settings are correct.

Check that the starting frequency (Pr. 13) setting is not greater than the running frequency.

Check that various operational functions (such as three-speed operation), especially the maximum frequency (Pr. 1), are not zero.

Manual background 4) Check the load

Check that the load is not too heavy. Check that the shaft is not locked.

Manual background 5) Others

Check that the operation panel display does not show an error (e.g. OC1). Check that the Pr. 15 "jog frequency" setting is not lower than the Pr. 13 "starting frequency" value.

166

Page 176
Image 176
Mitsubishi Electronics FR-S500 instruction manual Troubleshooting, Motor remains stopped