Mitsubishi Electronics FR-S500 instruction manual Three-wire type connection STF, STR, STOP

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 36
Image 36
(2) Three-wire type connection (STF, STR, STOP)

Input terminals

(2) Three-wire type connection (STF, STR, STOP)

 

 

 

 

 

A three-wire type connection is shown on

 

 

 

 

 

 

NFB

 

 

 

 

 

the right. Assign the start self-holding

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

R, S, T

signal (STOP) to any of the input terminals.

 

 

 

 

 

 

 

supply

Forward

Inverter

To make a reverse rotation start, set Pr. 63

 

Stop

rotation start

to "- - -" (factory setting).

 

 

 

 

 

 

 

 

 

STF

 

 

 

 

 

 

 

 

1) Short the signals STOP-SD to enable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the start self-holding function. In this

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STR (Pr.63= "- - -" )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reverse

case, the forward/reverse rotation signal

 

 

 

 

 

 

 

 

 

 

 

 

functions only as a start signal.

 

 

 

 

 

 

 

rotation start

STOP

 

 

 

 

 

 

 

 

 

 

 

 

(Note) Assign the stop signal to any of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SD

Pr. 60 to Pr. 62 (input terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

function selection).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2) If the start signal terminals STF (STR)-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SD are shorted once, then opened, the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

start signal is kept on and starts the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inverter. To change the rotation direction,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time

short the start signals STR (STF)-SD

 

Output

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

once, then open it.

Start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3) The inverter is decelerated to a stop by

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

opening the signals STOP-SD once. For

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the frequency setting signal and the

Stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation of DC injection brake at a stop

 

 

 

 

3-wire type connection example

time, refer to paragraphs 2) to 4) in (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Two-wire type connection. The right diagram shows 3-wire type connection.

4)When the signals JOG-SD are shorted, the STOP signal is invalid and the JOG signal has precedence.

5)If the output stop signals MRS-SD are shorted, the self-holding function is not deactivated.

DC Injection Brake and Coasting to Stop Functionality

Operation

External Operation or Combined

PU Operation or Combined

Operation

Operation

Mode

Pr. 79 = "0", "2", "3"

Pr. 79 = "0", "1", "4"

 

Terminals STF

Set frequency

 

Set frequency

 

(STR)-SD

Stop key

DC

disconnected

changed to 0Hz

changed to 0Hz

 

Brake

(*1)

 

 

 

 

DC injection brake

 

DC injection brake

 

 

operated at not

DC injection brake

operated at not

DC injection brake

DC injection

more than "DC

more than "DC

injection brake

operated at 0.5Hz

injection brake

operated at 0.5Hz

brake enabled

operation

or less.

operation

or less.

 

frequency" set in

 

frequency" set in

 

 

Pr. 10

 

Pr. 10

 

 

Coasted to a stop

 

Coasted to a stop

 

DC injection

at not more than

Coasted to a stop

at not more than

Coasted to a stop

"DC injection

"DC injection

brake disabled

brake operation

at 0.5Hz or less.

brake operation

at 0.5Hz or less.

 

frequency" set in

 

frequency" set in

 

 

Pr. 10

 

Pr. 10

 

*1: Also stopped by the RESETSTOP

. Refer to page 105.

 

 

 

26

 

 

Page 36
Image 36
Mitsubishi Electronics FR-S500 instruction manual Three-wire type connection STF, STR, STOP