Errors (Alarms)

(4) Write errors

Operation Panel Indication

Er1

 

FR-PU04

Control Mode

 

 

 

 

 

Name

Write disable

error

 

 

 

• Write was performed with "1" (write disable) set in Pr. 77

Description

"parameter write disable selection".

• Frequency jump setting range overlapped.

 

• Parameter write was performed though the operation panel does

 

not have the write precedence.

 

• Check the setting of Pr. 77 "parameter write disable selection".

 

(Refer to page 108.)

 

• Check the settings of Pr. 31 to 36 (frequency jump). (Refer to

Corrective action

page 80.)

• When the FR-PU04 is fitted and n17 = "0" or "1", the operation of

 

 

the operation panel is invalid.

 

For RS-485 connector (RS-485) communication, the operation of

 

the operation panel is invalid.

Operation Panel Indication

Er2

 

FR-PU04

In PU/EXT Mode

 

OPERATOR ERR

 

 

 

 

Name

Write-while-running error/mode designation error

 

• Write was performed during operation.

 

Description

• An attempt was made to change the Pr. 79 setting to the

operation mode where the operation command has been input.

 

Write was performed in the external operation mode.

After stopping operation, make parameter setting.

Corrective action • After setting the operation mode to the "PU operation mode",

make parameter setting. (Refer to page 109.)

Operation Panel Indication

Er3

 

FR-PU04

Incr I/P

 

 

 

 

 

Name

Calibration error

 

 

Description

Analog input bias and gain calibration values are too close.

Corrective action

Check the settings of C3, C4, C6 and C7 (calibration functions).

(Refer to page 82.)

 

 

 

 

 