Mitsubishi Electronics FR-S500 Extended function display selection Pr, Frequency jump Pr, to Pr

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 90
Image 90
2.3.15 Extended function display selection (Pr. 30 )

Explanation of functions (parameters)

2.3.15 Extended function display selection (Pr. 30 2.3.16 Frequency jump (Pr. 31)

Used to display the extended function parameters.

to Pr. 36 Refer to page 48 for the extended function parameter list.

Manual background Refer to the instruction manual (basic) for the parameter setting method.

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

30

Extended function

0

0, 1

0: Without display,

display selection

1: With display

 

 

 

2.3.16 Frequency jump (Pr. 31

to Pr. 36

)

When it is desired to avoid

 

 

Frequency jump

resonance attributable to the

(Hz)

 

natural frequency of a

Pr.36

 

3B

mechanical system, these

frequency

Pr.35

 

 

3A

parameters allow resonant

 

 

frequencies to be jumped. Up

Pr.34

 

2B

to three areas may be set,

Pr.33

 

with the jump frequencies set

Running

 

 

2A

to either the top or bottom

Pr.32

1B

 

point of each area.

Pr.31

 

1A

 

The value set to 1A, 2A or 3A

 

 

 

 

is a jump point and operation

 

 

 

 

is performed at this frequency.

 

 

 

 

Parameter

Name

Factory

Setting Range

Remarks

Setting

 

 

 

 

31

Frequency jump 1A

---

0 to 120Hz,---

 

32

Frequency jump 1B

---

0 to 120Hz,---

• - - -: Function invalid

33

Frequency jump 2A

---

0 to 120Hz,---

•Setting is enabled when Pr.

34

Frequency jump 2B

---

0 to 120Hz,---

30 = "1"

35

Frequency jump 3A

---

0 to 120Hz,---

 

36

Frequency jump 3B

---

0 to 120Hz,---

 

<Setting>

•To fix the frequency at 30Hz between Pr. 33 and Pr. 34

Pr.34:35Hz

(30Hz and 35Hz), set 30Hz in Pr. 33 and 35Hz in Pr. 34.

Pr.33:30Hz

 

•To jump to 35Hz between 30 and 35Hz, set 35Hz in

Pr.33:35Hz

Pr. 33 and 30Hz in Pr. 34.

Pr.34:30Hz

 

CAUTION

During acceleration/deceleration, the running frequency within the set area is valid.

REMARKS

Write disable error " Manual backgroundManual backgroundManual background " occurs if the frequency jump setting ranges overlap.

80

Page 90
Image 90
Mitsubishi Electronics FR-S500 instruction manual Extended function display selection Pr, Frequency jump Pr, to Pr, Setting