(1) PU operation interlock

Operation selection function parameters

(1) PU operation interlock

PU operation interlock forces the operation mode to be changed to the external operation mode when the MRS signal switches off. This function prevents the inverter from being inoperative by the external command if the mode is accidentally left unswitched from the PU operation mode.

1) Preparation

Set "7" (PU operation interlock) in Pr. 79.

Set the terminal used for MRS signal input with any of Pr. 60 to Pr. 63 (input terminal function selection).

Refer to page 98 for Pr. 60 to Pr. 63 (input terminal function selection).

CAUTION

When terminal assignment is changed using Pr. 60 to Pr. 63, the other functions may be affected.

Check the functions of the corresponding terminals before making settings.

2) Function

MRS Signal

Function/Operation

 

Output stopped during external operation.

ON

Operation mode can be switched to PU operation mode.

Parameter values can be rewritten in PU operation mode.

 

 

PU operation allowed.

 

Forcibly switched to external operation mode.

OFF

External operation allowed.

 

Switching to PU operation mode inhibited.

<Function/operation changed by switching on-off the MRS signal>

Operating

Condition

MRS

Operation

 

 

Parameter

Switching to

 

 

Operation

Status

Signal

Mode

Operating Status

Write

PUOperation

 

 

mode

(*2)

 

 

Mode

 

 

 

 

 

 

 

 

 

 

During

ON → OFF

 

During stop

Allowed →

Disallowed

 

 

 

stop

(*1)

 

disallowed

 

 

 

 

 

 

 

 

 

 

 

 

 

If external

 

 

 

2

PU

 

 

PU →

operation

 

 

 

During

ON → OFF

External

frequency setting

Allowed →

Disallowed

 

 

 

and start signal are

 

 

 

 

 

 

operation

(*1)

 

entered, operation

disallowed

 

FUNCTIONS

 

 

 

 

Disallowed →

 

 

 

 

 

is performed in that

 

 

 

 

 

 

 

 

 

 

 

 

 

status.

 

 

 

 

 

During

OFF → ON

 

During stop

 

disallowed

Allowed

 

 

 

 

 

 

 

 

 

 

stop

ON → OFF

 

 

Disallowed →

Disallowed

 

 

 

 

 

 

 

 

External

 

 

External

 

 

disallowed

 

 

 

During

OFF → ON

During operation →

Disallowed →

Disallowed

 

 

 

 

 

output stop

disallowed

 

 

 

 

operation

ON → OFF

 

Output stop →

Disallowed →

Disallowed

 

 

 

 

 

 

operation

disallowed

 

 

 

111

Page 121
Image 121
Mitsubishi Electronics FR-S500 PU operation interlock, Function/operation changed by switching on-off the MRS signal