Mitsubishi Electronics FR-S500 Wiring of RS-485 communication, System configuration examples

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 52
Image 52
1.7.2Wiring of RS-485 communication

Handling of the RS-485 connector

1.7.2Wiring of RS-485 communication

Use the RS-485 connector to perform communication operation from a personal computer etc.

When the RS-485 connector is connected with a personal, FA or other computer by a communication cable, a user program can run and monitor the inverter or read and write to the parameters. For parameter setting, refer to page 130.

•Conforming standard: EIA-485 (RS-485)

•Transmission format: Multidrop link system

•Communication speed: Max. 19200bps

•Overall extension: 500m

<System configuration examples>Refer to page 130 for the setting related to RS-485 communication operation.

<System configuration examples>

(1) Connection of a computer to the inverter (1:1 connection)

Computer

Station 0

 

 

Computer

Station 0

 

 

 

Inverter

 

 

RS-232C

Inverter

 

 

 

RS-485

 

 

connector

RS-485

 

 

 

RS-232C

 

 

 

 

 

 

RS-485

 

 

connector

cable

 

 

 

Max. 15m

connector

 

 

 

 

 

 

 

 

 

 

 

interface/

 

 

 

 

 

RS-232C RS-485

 

 

 

terminal

 

 

 

 

 

converter

 

 

RJ-45 connector 2)

 

 

 

 

RJ-45 connector 2)

 

 

 

 

 

 

 

 

 

10BASE-T cable 1)

 

 

 

 

10BASE-T cable 1)

(1) Connection of a computer to the inverter (1:1 connection) Computer-inverter connection cable

Refer to the following for the cable (RS-232CRS-485 converter) for connection of the computer having the RS-232C interface with the inverter.

Example of product available on the market (as of April, 2004)

Model

Maker

FA-T-RS40 *

Mitsubishi Electric Engineering Co., Ltd.

*The converter cable cannot connect two or more inverters (the computer and inverter are connected on a 1:1 basis). Since the product is packed with the RS- 232C cable and RS-485 cable (10BASE-T + RJ-45 connector), the cable and connector need not be prepared separately.

REMARKS

Refer to the following when fabricating the cable on the user side.

Example of product available on the market (as of April, 2004)

 

Product

Model

Maker

1)

10BASE-T cable

SGLPEV-T 0.5mm × 4P

Mitsubishi Cable Industries, Ltd.

* Do not use pins No. 2, 8 (P5S).

2)

RJ-45 connector

5-554720-3

Tyco Electronics Corporation

42