Errors (Alarms)

Operation Panel Indication

OV1

 

 

FR-PU04

OV During Acc

 

 

 

 

 

Name

Regenerative

overvoltage shut-off during

acceleration

 

When the main circuit DC voltage in the inverter rises to or above

Description

the specified value due to excessive regenerative energy during

acceleration, the protective circuit is activated to stop the inverter

 

output. The circuit may also be activated by a surge voltage

 

produced in the power supply system.

 

Check point

Check for too slow acceleration. (e.g. during downward

acceleration in vertical lift load)

 

 

 

 

 

Corrective action

• Decrease the acceleration time.

 

• Install a power factor improving reactor.

 

 

 

Operation Panel Indication

OV2

 

 

FR-PU04

Stedy Spd OV

 

 

 

 

 

Name

Regenerative

overvoltage shut-off during constant speed

 

When the main circuit DC voltage in the inverter rises to or above

Description

the specified value due to excessive regenerative energy during

constant speed, the protective circuit is activated to stop the inverter

 

output. The circuit may also be activated by a surge voltage

 

produced in the power supply system.

 

Check point

Check for sudden load change.

 

 

Corrective action

• Keep load stable.

 

 

• Install a power factor improving reactor.

 

 

 

Operation Panel Indication

OV3

 

FR-PU04

 

OV During Dec

 

 

 

 

 

Name

Regenerative

overvoltage shut-off during

deceleration or stop

 

When the main circuit DC voltage in the inverter rises to or above

Description

the specified value due to excessive regenerative energy during

deceleration or stop, the protective circuit is activated to stop the

 

inverter output. The circuit may also be activated by a surge

 

voltage produced in the power supply system.

 

Check point

Check for sudden speed reduction.

 

 

• Increase the deceleration time. (Set the deceleration time which

Corrective action

matches the moment of inertia of the load)

 

• Decrease the braking duty.

 

 

 

 

 

 

 

 

• Install a power factor improving reactor.

 

158

Page 168
Image 168
Mitsubishi Electronics FR-S500 instruction manual OV During Acc, Stedy Spd OV, OV During Dec