2.11.2 Automatic torque boost selection (Pr. 98 )

Auxiliary parameters

2.11.2 Automatic torque boost selection (Pr. 98 <Operating conditions>)

You can choose automatic torque boost control.

Manual backgroundAutomatic torque boost control

Not only gives the motor the optimum excitation but also provides high torque even in a low speed range.

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

98

Automatic torque boost

- - -

0.1 to 3.7kW,

Setting is enabled when

selection (motor capacity)

- - -

Pr. 30 = "1"

 

 

<Operating conditions>

The number of motor poles should be any of 2, 4 and 6 poles.

Single-motor operation (One motor for one inverter)

The wiring length from inverter to motor should be within 30m (98.42feet).

<Setting>

Parameter

Setting

Description

98

- - -

Ordinary V/F control and torque boost (Pr. 0, Pr. 46) are valid.

0.1 to 3.7kW

Automatic torque boost control valid

 

 

(Set the applied motor capacity or one rank lower motor capacity.)

Also when the Pr. 98 setting is other than "- - -", Pr. 3 "base frequency" and Pr. 19 "base frequency voltage" are valid.

When "- - -" or "888" is set in Pr. 19, the rated output voltage is selected.

CAUTION

During operation using automatic torque boost, write to Pr. 3 and Pr. 19 is disabled even if "2" is set in Pr. 77.

Related parameters

Torque boost ⇒ Pr. 0 "torque boost", Pr. 46 "second torque boost" (refer to page 63)

Base frequency ⇒ Pr. 3 "base frequency", Pr. 19 "base frequency voltage" (refer to page 65)

Applied motor setting ⇒ Pr. 71 "applied motor" (refer to page 69)

• Motor primary resistance ⇒ Pr. 99 "motor primary resistance" (refer to page 122)