Mitsubishi Electronics FR-S500 PWM carrier frequency Pr. 70 , Pr, Setting, Refer to page

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 113
Image 113
2.10.2 PWM carrier frequency (Pr. 70 , Pr. 72 )

Operation selection function parameters

2.10.2 PWM carrier frequency (Pr. 70 You can change the motor sound., Pr. 72  Refer to  (page 69).)

You can change the motor sound.

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

70

Soft-PWM setting

1

0, 1

Setting is enabled when

72

PWM frequency selection

1

0 to 15

Pr. 30 = "1"

<Setting>

By parameter setting, you can set whether to exercise Soft-PWM control that changes the motor tone.

Soft-PWM control is a control system that changes the motor noise from a metallic tone into an unoffending complex tone.

Pr.70 Setting

Description

0Soft-PWM invalid

1When Pr. 72="0 to 5", Soft-PWM is made valid.

Pr.72 Setting

Description

 

PWM carrier frequency can be changed.

0 to 15

The setting displayed is in [kHz].

 

Note that 0 indicates 0.7kHz and 15 indicates 14.5kHz.

REMARKS

•An increased PWM frequency will decrease the motor sound but increase noise and leakage currents. Therefore, perform the reduction techniques. (Refer to page 18.)

•Metallic sound may be generated from the motor at sudden deceleration but it is not a fault.

Manual backgroundManual background Refer to Manual background (page 69).

2

FUNCTIONS

103

Page 113
Image 113
Mitsubishi Electronics FR-S500 PWM carrier frequency Pr. 70 , Pr, Setting, You can change the motor sound, Refer to page