Mitsubishi Electronics FR-S500 Setting, Refer to the following table and set the parameters

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 103
Image 103
Refer to the following table and set the parameters:

Restart operation parameters

<Setting>

Refer to the following table and set the parameters:

Parameter

 

Setting

Description

 

0

0.1K to 1.5K

Coasting time of 0.5s

Generally, this setting will pose

 

 

2.2K, 3.7K

Coasting time of 1.0s

no problems.

57

 

 

Waiting time for inverter-triggered

restart after power is restored

 

0.1 to 5s

from an instantaneous power failure. (Set this time between 0.1

 

 

 

 

and 5s according to the moment (J) of inertia and torque of the

 

 

 

 

 

 

load.)

 

58

 

- - -

No restart (factory setting)

 

 

0 to 60s

Normally the motor may be run with the factory settings. These

 

 

values are adjustable to the load (moment of inertia, torque).

 

 

 

 

 

 

With speed search

 

 

 

0

The motor coasting speed is detected after instantaneous power

 

 

 

failure is detected.

 

 

 

 

Without speed search (factory setting)

H6 (162)

 

1

Automatic restart operation after instantaneous power failure is a

 

reduced voltage starting system in which the output voltage is

 

 

 

risen gradually at the preset frequency independently of the

 

 

 

coasting speed of the motor.

 

 

 

 

With speed search at starting

 

 

 

10

The motor coasting speed is detected after instantaneous power

 

 

 

failure and at starting.

 

H6 = 0, 10 (with speed search)

Instantaneous power failure (power failure) time

H6 = 1 (without speed search)

Instantaneous power failure (power failure) time

Power supply (R, S, T)

STF(STR)

Motor speed (r/min)

Inverter output

frequency* (Hz)

Inverter output voltage

(V)

Coasting time

Pr. 57 setting

Speed search time (300ms maximum)

Restart voltage cushion time Pr. 58 setting

Power supply (R, S, T)

STF(STR)

Motor speed (r/min) Inverter output frequency (Hz)
Inverter output voltage

(V)

Restart voltage cushion time Pr. 58 setting * Power supply (R, S, T)

 

Restart

Coasting time

voltage

Pr. 57 setting

cushion time

 

 

Pr. 58 setting

2

FUNCTIONS

*The output shut off timing differs according to the load condition.

93

Page 103
Image 103