2.3 Explanation of functions (parameters)

Explanation of functions (parameters)

2.3 Explanation of functions (parameters)

2.3.1

Torque boost (Pr. 0

, Pr. 46

)

 

Increase this value for use when the

 

 

voltage

 

inverter-to-motor distance is long or

 

 

 

motor torque is insufficient in the low

 

 

 

 

 

Output

 

speed range (stall prevention is

 

 

 

activated).

 

 

 

Motor torque in the low-frequency

Pr.0

 

 

 

range can be adjusted to the load to

Setting range

 

Pr.46

 

increase the starting motor torque.

 

 

0

Output frequency (Hz)

 

 

 

 

Parameter

Name

Factory Setting

Setting Range

Remarks

 

 

 

 

The factory setting varies according

0

Torque boost

6%/5%/4%

0 to 15%

to the inverter capacity. (Refer to the

 

 

 

 

following table for details.)

46

Second torque

- - -

0 to 15%,

- - -: Function invalid. Setting is

boost

- - -

enabled when Pr. 30 = "1".

 

 

<Setting>

Assuming that the base frequency voltage is 100%, set the 0Hz voltage in %.

Use the RT signal to switch between two different torque boosts. (Turn on the RT signal to make Pr. 46 valid(*).)

REMARKS

* The RT signal acts as the second function selection signal and makes the other second functions valid.

2.3.1 When using an inverter-dedicated motor (constant-torque motor), make setting as indicated below.

(If the factory set Pr. 71 value is changed to the setting for use with a constant-torque motor, the Pr. 0 setting changes to the corresponding value in the following table.)

Inverter Type

Inverter Capacity

Factory Setting

Constant-torque Motor Setting

FR-S520E

 

0.1K to 0.75K

6%

6% (no change)

FR-S510WE

1.5K to 3.7K

4%

 

 

 

0.4K, 0.75K

6%

6% (no change)

FR-S540E

 

1.5K

5%

4%

 

2.2K

3%

 

 

 

 

 

3.7K

4%

 

 

 

CAUTION

Selecting automatic torque boost control makes this parameter setting invalid.

A too large setting may cause the motor to overheat or result in an overcurrent trip. The guideline is about 10% at the greatest.

Related parameters

RT signal (second function "Pr. 46") setting⇒ Pr. 60 to Pr. 63 "input terminal function selection" (refer to page 98)

Constant-torque motor setting ⇒ Pr. 71 "applied motor" (refer to page 69)

Automatic torque boost control selection ⇒ Pr. 98 "automatic torque boost selection (motor capacity)" (refer to page 121)