Mitsubishi Electronics FR-S500 instruction manual Design information

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 55
Image 55
1.8 Design information

Design information

1.8 Design information

1)Provide electrical and mechanical interlocks for MC1 and MC2 which are used for commercial power supply-inverter switchover.

When the wiring is incorrect or if there is a commercial power supply-inverter switch-over circuit as shown below, the inverter will be damaged by leakage current from the power supply due to arcs generated at the time of switchover or chattering caused by a sequence error.

2)If the machine must not be restarted when power is restored after a power failure, provide a magnetic contactor in the inverter's primary circuit and also make up a sequence which will not switch on the start signal.

If the start signal (start switch) remains on after a power failure, the inverter will automatically restart as soon as the power is restored.

3)Since the input signals to the control circuit are on a low level, use two or more parallel micro signal contacts or a twin contact for contact inputs to prevent a contact fault.

4)Do not apply a large voltage to the contact input terminals (e.g. STF) of the control circuit.

5)Always apply a voltage to the alarm output terminals (A, B, C) via a relay coil, lamp etc.

6)Make sure that the specifications and rating match the system requirements.

1) Commercial power supply-inverter

3) Low-level signal contacts

switchover

 

 

 

 

MC1

 

 

Power

R

U

Interlock

 

 

 

 

 

supply

IM

 

 

S

V

 

 

 

MC2

 

 

 

T

W

Leakage current

Low-level signal contacts

Twin contact

 

Inverter

 

 

 

 

 

1

WIRING

45

Page 55
Image 55
Mitsubishi Electronics FR-S500 instruction manual Design information