Operation selection function parameters

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

Name

Setting

 

 

Description

Number

 

 

 

 

 

 

 

 

 

 

Set the upper limit. If the feedback value exceeds the

91

PID upper

0 to 100%

setting, the FUP signal is output. (Measured value of

limit

 

4mA is equivalent to 0% and 20mA to 100%.)

 

 

 

 

- - -

No function

 

 

 

Set the lower limit. (If the measured value falls below

 

PID lower

0 to 100%

the setting, the FDN signal is output. In this case, the

92

measured value of 4mA is equivalent to 0% and 20mA

 

limit

 

to 100%.)

 

 

 

 

 

- - -

No function

 

 

 

Valid only when Pr. 79 = "3" (n9 = 0 for computer link

 

 

 

operation) under the PU command in the PU operation

 

PID action

 

or PU/external combined mode. (When the computer

 

 

has the speed command source in the computer link

93

set point for

0 to 100%

operation mode (NET))

 

PU operation

 

For external operation, the voltage across 2-5 is the set

 

 

 

 

 

 

point.

 

 

 

(C3 value is equivalent to 0% and C4 value to 100%.)

 

PID

 

Time required for the differential (D) action to provide

 

0.01 to 10s

the same measured value as that for the proportional

94

differential

(P) action. As the differential time increases, greater

 

time

 

response is made to a deviation change.

 

 

- - -

No differential control.

(6) Adjustment procedure

Parameter setting

Adjust the PID control parameters, Pr. 88 to Pr. 94.

 

 

 

Terminal setting

Set the I/O terminals for PID control.

 

 

(Use Pr. 64 and Pr. 65 (output terminal function selection) to set the

 

 

 

 

FUP and FDN signals.)

 

 

(Use any of Pr. 60 to Pr. 63 (input terminal function selection) to set

 

 

the X14 signal.)

Turn on X14 signal.

 

 

 

 

 

 

Run

 

2

FUNCTIONS

117

Page 127
Image 127
Mitsubishi Electronics FR-S500 instruction manual Adjustment procedure