Explanation of functions (parameters)

2.3.7DC injection brake (Pr. 10 , Pr. 11 , Pr. 12 )

By setting the DC injection brake voltage (torque), operation time and operation starting frequency, the stopping accuracy of positioning operation, etc. or the timing of operating the DC injection brake to stop the motor

Output frequency (Hz)

Pr.10

"Operation

frequency"

can be adjusted according to the load.

Pr.12

Time

DC injection brake voltage

"Operation voltage"

Time

Pr.11 "Operation time"

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

DC injection brake

Setting is enabled when

10

3Hz

0 to 120Hz

 

operation frequency

 

 

Pr. 30 = "1".

11

DC injection brake

0.5s

0 to 10s

(When Pr. 11 is set to "0s" or

operation time

Pr. 12 is set to "0%", DC

12

DC injection brake voltage

6%

0 to 15%

injection brake is not

operated.)

* The factory setting varies according to the inverter capacity. (Refer to the following table for details.)

<Setting>

Use Pr. 10 to set the frequency at which the DC injection brake operation is started.

Use Pr. 11 to set the period during when the brake is operated.

Use Pr. 12 to set the percentage of the power supply voltage.

Change the Pr. 12 setting to 4% when using the inverter-dedicated (constant-torque motor).

(If the Pr. 12 value remains unchanged from the factory setting and Pr. 71 is changed to the setting for use of the constant-torque motor, the Pr. 12 setting is automatically

changed to 4%.)

.

CAUTION

Install a mechanical brake. No holding torque is provided.

2

FUNCTIONS

71

Page 81